ADD FURNACE CO.,LTD.
44 ซอยบรมราชชนนี

โทร: 02-888-3472 โทร (.บบแกออ) :08-08-170-170 กฟแซ์: 02-888-3258
https://www.add-furnace.com E-mail: sales@add-furnace.com
4.3.1.2 Timer Example-2
Once digital input high event is triggered say pressure high, you would like switch
on relay after a delay of 10 sec
Digital Input1
Event1
Type: H
Job1: Enable Timer, Target: Timer1
Job2: No Action
Event2
Type: L
Job1: DO Latch Off, Target: DO1
Job2: No Action
Timer1
Type: Countdown, Action: Disable
Time Hour: 0 Min: 0 Sec: 10
Job1: DO Latch On, Target: DO1
Job2: No Action
4.3.1.3 Timer Example-3
Timer & Report:
A staff plans to get a daily report from the recorder about the minimum,
maximum and average values of the process every day. After the production has
finished, he can press Menu, then Event, select Report and press Mode key to
select Daily mode and get the report like figure shown below
Timer1
Type: Daily Action: Enable
Time Hour: 17 Min: 01
Job1: Log Report Target: ALL CH MinMaxAve
Job2: Reset MinMaxAve Target: ALL CH
(Reset historical data in order to logging new data for the next day.)