Setpoint: Defines the set point of process value to trigger the totalizer.
Job1, Job2: various jobs as described in 4.1 Channel, 2 jobs for each totalizer.
An example of Totalizer: A factory operates for 8 hours a day, and the staff wish to get the total volume
of production from daily, weekly and monthly reports. First, the user needs to enter into Tools mode, do
the settings as follows, then totalizer starts to work from 8:30 am, and stops at 17:30 pm daily. After
production has finished, the user does the following: press Event key on the left hand side, and press Mode
key to select Report mode. Finally, press Report key to choose daily, weekly or monthly report.
Timer1 Timer2
Type: Daily Action: Enable Type: Daily Action: Enable
Time: Hour: 8 Min: 30 Time: Hour: 17 Min: 30
Job1: Reset Totalz Target: Tolz1 Job1: Log Report Target: Tolz1
Job2: Enable Totalz Target: Tolz1 Job2: Disable Totalz Target: Tolz1
Timer3 Timer4
Type: Weekly Action: Enable Type: Weekly Action: Enable
Time: Hour: 17 Min: 31 Time: Hour: 8 Min: 00
Job1: Disable Timer Target: Timer1 Job1: Enable Timer Target: Timer1
Job2: Disable Timer Target: Timer2 Job2: Enable Timer Target: Timer2
Totalizer
Name: xxxx Desc : xxxxxxxxxxxxxxxxx
Source: AI1 Action: Enable Decimal: 1
Period: Min Unit: xxxx Preset: 0.0
Event
No Type Setpoint Job1 Job2
1 High xxxx Log Alarm Set DO Process
2 Low xxxx Log Alarm Set DO Process
The daily, weekly or monthly report indicates Totalizer data of each day, each week or each month
respectively.