Additional features of the E16x442-System:
Remote test of solenoid valve block by test signals from DCS possible
Display in each module for measured values and diagnostics
Alarm outputs via opto-relays to DCS
Free extra alarm from each monitor
Up to 6 speed setpoints with 2oo3 logic outputs (if voters are not required)
Sensor signal repeater outputs, free floating and push/pull
Optional Analog Output (to represent the speed) 0/4..20 mamps for each monitor
Direction alarm (only with sensors type A5S with direction output)
Parameters may be set by front keys (protected by code-digit) or by
RS232-Interface (password protected)
E16x442.abc
c = 1 : Speed Signal Inputs and power supply for A5S sensors
c = 2 : Speed Signal Inputs and power supply for Eddy Current Sensors
c = 3 : Speed Signal Inputs for MPU (magnetic pick up)
b = 1 : 1 Voter in each Monitor for external trip release condition
b = 2 : 6 Voters in each Monitor for external trip release conditions
a = 0 : without Analog Output (to represent the speed)
a = 1 : 1 Analog Output in each Monitor A, B, C
a = 2 : 1 Analog Output rated SIL2 in each Monitor A, B, C
x = A : Surface Mount Version
x = E : 19-Inch Rack File
x = G : Nema 4 Version with front window (surface mount)
Example:
E16A442.021 : Surface Mount Version, without Analog Output, with 6 Voters,
Speed Signal Inputs for A5S sensors
E16A442.112 : Surface Mount Version, with Analog Output, with 1 Voter,
Speed Signal Inputs for eddy current sensors or MPU
E16A442.013 : Surface Mount Version, with 1 Voter,
Speed Signal Inputs for MPU