EasyManuals Logo

Brivis BX3C User Manual

Brivis BX3C
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
Rinnai 12 Ducted Gas Heater IM
Table 1. Ventilation F Factors
Gas appliance location Source of Ventilation Factor F
Gas appliance in a room or enclosure
Directly to outside* 300
Via an adjacent room 600
Gas appliance in a plant room
Directly to outside* 150
Via an adjacent room 300
Gas appliance in a residential garage Directly to outside* 300
* Directly to outside means through an external wall to outside, into a cavity vented to outside,
into an underfloor space vented to outside, or into a roof space vented to outside.
Installation of a gas appliance in a room or enclosure for properties approved for construction AFTER
March 31
st
2014
a. Determine if the rating per cubic metre of the space is greater than 0.4 MJ/hr per m³.
Example:
Unit rating (Ur) = 120MJ/hr
Room volume (Rv) = 1m x 1m x 2.4m = 2.4m
3
Ur/Rv = 120/2.4 = 50 MJ/hr per m
3
As the result is greater than 0.4 MJ/hr per cubic metre of the space, additional ventilation is required.
Refer to AS/NZS 5601 for natural ventilation requirements.
NOTE
For New Zealand ventilation requirements and all other applications, e.g. Mechanical Ventilation,
refer AS/NZS 5601.
GENERAL PRODUCT GUIDELINES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Brivis BX3C and is the answer not in the manual?

Brivis BX3C Specifications

General IconGeneral
BrandBrivis
ModelBX3C
CategoryGas Heater
LanguageEnglish

Related product manuals