7-3
8. The maintenance report, with recom-
mendations if any, shall be filed with
the owner or with the designated party
responsible for the system.
9. The service personnel shall date and
sign the Semi-Annual Inspection &
Maintenance Log contained in this
manual as an indication that the
inspection has been completed.
Twelve Year Maintenance
Maintenance must be done on the fire sup-
pression system every twelve years. The
maintenance must be performed by certi-
fied service personnel per NFPA 17A and
includes the following:
1. The wet chemical extinguishing agent
must be removed and discarded.
2. The cylinder needs to be hydrostati-
cally tested.
Certified service personnel
can generally be found
locally through authorized suppliers of fire
extinguishing equipment in the yellow
pages or call your Broaster Distributor for
sources.
3. If the cylinder shows no signs of rup-
ture or distortion, recharge the Fire
Suppression system in accordance
with NFPA 17A guidelines.