54 S5 Battery Validation System
2
Go to the Controller
Settings window.
a. In the Communications window, click
Advanced>> to display the lower buttons.
b. Click the Controller Settings button.
3
See how many units
(voltage modules)
are installed and
which limits have
been assigned to
them.
From the Controller Settings window, click on
the Unit Limits tab to select the limit set for each
unit.
Note that in this example, there are four sets of
limits, reflected by the tabs Unit Limit Set 1, Unit
Limit Set 2, Unit Limit Set 3, and Unit Limit Set
4.
4
View the limits for
voltage, impedance,
and temperature.
Click on one of the Unit Limit Set tabs in the
Controller Settings window.
• The maintenance limits show the upper and
lower ranges of normal battery performance.
If the battery readings exceed this range, a
maintenance alarm will be created and you
will be notified by e-mail that maintenance
should be performed.
• The critical limits show the upper and lower
ranges of battery performance under stress. If
the battery readings exceed this range, a
battery failure is likely to occur soon, and a
critical alarm will be created. You will also be
notified by e-mail that you should correct the
situation immediately.
Action How to do it Picture