C−LRV lift control valve Installation and commissioning
57/92
300−I−9010212−E−10/08.08
4.3.6 Speed−monitoring in the door zone, SIU−4
The SIU−4 function monitors the speed in the door zone and during
relevelling. If the speed setting is exceeded, the lift is stopped (per EN
81−2, max. 0.3 m/s)
S When the speed setting is exceeded, the relay activates
S The speed can be set with the Handterminal or PC software
4.3.7 The inspection−travel speed setting
To set the inspection−travel speed, see the Options menu ⇒ 5.1.4.2, the
parameter "Inspection speed".