EasyManuals Logo

Bucher C-LRV Series User Manual

Bucher C-LRV Series
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #67 background imageLoading...
Page #67 background image
CLRV lift control valve Operation
67/92
300−I−9010212−E−10/08.08
5.1.4 Description of parameters
5.1.4.1 Demand values Up / Down (1)
Setting "Start speed"
S Higher value: faster starting speed, shorter starting time, harsher
start−up jolt
S Setting range: 0.05–0.50V
S Standard: 0.30V
Important: low settings for "Start speed" may cause long starting times
Setting "Min. pressure" (UP)
S Operative during Up travel
S Higher value: higher solenoid starting voltage, shorter starting time
S Setting range: 5.0–100.0bar
S Standard: 20.0bar
Important: high settings may cause a start−up jerk.
Setting "Offset sol." (DOWN)
S Operative during Down travel
S Higher value: higher solenoid starting voltage, shorter starting time
S Setting range: 1.00–7.00V
S Standard: 4.00V
Important: high settings may cause a start−up jerk.
Setting "Acceleration"
S Higher value: greater acceleration, i.e. shorter acceleration distance
S Setting range: 0.30–5.00V/s
S Standard: 2.00V/s

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bucher C-LRV Series and is the answer not in the manual?

Bucher C-LRV Series Specifications

General IconGeneral
BrandBucher
ModelC-LRV Series
CategoryControl Unit
LanguageEnglish

Related product manuals