C−LRV lift control valve Operation
68/92
300−I−9010212−E−10/08.08
Setting "Fast speed"
S Higher value: faster travel speed
S Setting range: 1.00–10.00V
S Standard: 7.00V
S Example of litres <=> volts conversion, ⇒ Page 79
Setting "Deceleration"
S Higher value: greater deceleration, i.e. shorter deceleration distance
S Setting range: 0.30–5.00V/s
S Standard: 3.00V/s
Setting "Slow speed"
S Operative after fast travel
S Higher value: faster travel speed
S Setting range: 0.20–2.50V
S Standard: 0.40V
Important: low settings for "Slow speed" may cause slow travel to be
uneven due to static friction in the cylinder and car guides
Important: low settings for "Slow speed" and "Soft−Stop" may cause
slight variations in levelling accuracy.
Setting "Soft−Stop"
S Higher value: greater deceleration, i.e. shorter stopping distance,
harsher stopping jolt
S Setting range: 0.20–5.00V/s
S Standard: 1.00V/s
S To disable : set to 5.00V/s
Important: low settings for "Slow speed" and "Soft−Stop" may cause
slight variations in levelling accuracy.