EasyManuals Logo

Bucher C-LRV Series User Manual

Bucher C-LRV Series
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #69 background imageLoading...
Page #69 background image
CLRV lift control valve Operation
69/92
300−I−9010212−E−10/08.08
Setting "Relevelling"
S Operative during fine adjustment
S Higher value: faster travel speed
S Setting range: 0.20–1.50V
S Standard: 0.40V
Important: low settings for "Relevelling" may cause slow travel to be
uneven due to static friction in the cylinder and car guides
Important: low settings for "Relevelling" and "Soft−Stop" may cause
slight variations in levelling accuracy.
Setting "P sol. static"
S Operative in steady−state control processes (constant−speed travel)
S Higher value: higher solenoid control gain
S Setting range: 0.20–1.50
S Standard: UP 0.80
DOWN 0.70
Important: high settings may cause oscillations.
Setting "I sol. static"
S Operative in steady−state control processes (constant−speed travel)
S Higher value: longer solenoid reset time
S Setting range: 100–1000ms
S Standard: UP 900ms
DOWN 700ms
Important: low settings may cause oscillations.
Setting "D sol."
S Higher value: longer solenoid derivative time
S Setting range: 0–100ms
S Standard: 20ms
S To disable, set to: 0ms
Important: high settings may cause oscillations.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bucher C-LRV Series and is the answer not in the manual?

Bucher C-LRV Series Specifications

General IconGeneral
BrandBucher
ModelC-LRV Series
CategoryControl Unit
LanguageEnglish

Related product manuals