CLRV lift control valve Operation
70/92
300−I−9010212−E−10/08.08
Setting "P sol. dynamic"
S Operative in dynamic control processes (acceleration, deceleration)
S Higher value: higher solenoid control gain
S Setting range: 0.20–1.50
S Standard: UP 0.80
DOWN 0.70
Important: high settings may cause oscillations.
Setting "I sol. dynamic"
S Operative in dynamic control processes (acceleration, deceleration)
S Higher value: longer solenoid reset time, greater control error in
dynamic processes
S Setting range: 100–1000ms
S Standard: UP 450ms
DOWN 350ms
Important: low settings may cause oscillations.
Setting "Calibr. factor"
S Valve calibration (feedback)
S Setting range: 0.90 − 1.30
S Standard: 1.00