C−LRV lift control valve Operation
72/92
300−I−9010212−E−10/08.08
Setting "SIU−1 difference"
S Demand/feedback difference − only operative when SIU−1 is activated
S Setting range: 20–50% of fast travel speed
S Standard: 25%
Setting "SIU−4 threshold"
S Feedback threshold − only operative when SIU−4 is activated
S Setting range: 2.0–5.0V
S Standard: 2.5V
Determining the SIU−4 threshold:
Car speed Fast UP
x = ... [Volt]
Speed in door zone
Dem. value Fast UP
Setting "Accel. inspection"
S Only operative with inspection speed (K5)
S Higher value: greater acceleration, i.e. shorter acceleration distance
S Setting range: 0.30–5.00V/s
S Standard: 2.00V/s
Setting "Inspection speed"
S K5 gives inspection speed
S Higher value: faster travel speed
S Setting range: 20–80% of fast travel speed
S Standard: 50%
Important: only operative with fast travel speed
Setting "Decel. inspection"
S Only operative with inspection speed (K5)
S Higher value: greater deceleration, i.e. shorter deceleration distance
S Setting range: 0.30–10.00V/s
S Standard: 4.00V/s