Servicing5
Wall-mounted condensing gas boiler Buderus 800 - Subject to modifications resulting from technical improvements!
54
5.3.11 Replacing the mains-water sensor
Unplug cable connection from mains-water sensor.
Pull mains-water sensor out and push new unit in.
Plug in cable connection.
5.3.12 Checking the cables to the flow, return and safety
sensors, and to the burner thermostat
Check to ensure that all plug-in connections to the
sensors/burner thermostat and in the UBA are in
order. Note that an incorrectly-inserted plug can lead to
the generation of error messages. Start up the boiler by
pressing the “reset” button.
Set the mains switch to “0”.
Disconnect the system from the power supply.
Unplug the cable connection from the sensor/burner
thermostat.
Check the cable between the plug-in connection and
the
24-pin plug in the UBA with a continuity tester.
If the cables are in order, plug them in.
Connect system to mains power supply.
Set the mains switch to “I”.
fig. 69 Outside temperature sensor diagram
Outside temperature sensor
(˚C)
R (Ω)
0
5
10
15
20
25
-20
-15
-10
-5
50,00020,000 80,00040,00030,00010,000 60,000 70,000
fig. 70 Replacing the mains-water sensor
fig. 71 Checking the cable to the flow/return sensors
Rear side
of UBA
Flow sensor
Retur n sensor
Red wire slee ve