Servicing5
Wall-mounted condensing gas boiler Buderus 800 - Subject to modifications resulting from technical improvements!
56
5.3.13 Checking the burner thermostat
Unplug cable connection from burner thermostat.
Allow burner thermostat to cool down (activation tem-
perature 107 °C).
Check burner thermostat for throughput. If no
throughput is detected, the burner thermostat is de-
fective.
If the burner thermostat is working correctly, plug it in
once more.
5.3.14 Replacing the burner thermostat
Pull cable lugs off.
Unscrew burner thermostat and screw in new unit.
Reconnect cable lugs and plug in once more.
5.3.15 Checking the hot surface ignitor
Disconnect the system from the power supply.
Unplug the hot surface ignitor.
Measure the resistance of the hot surface ignitor at
the plug. If the resistance is less than 200 , the hot
surface ignitor is in order.
Disconnect measuring device.
If the hot surface ignitor is working correctly, plug it in
once more.
Connect system to mains power supply.
fig. 74 Checking the burner thermostat
fig. 75 Replacing the burner thermostat
fig. 76 Checking the hot surface ignitor