Servicing 5
Wall-mounted condensing gas boiler Buderus 800 - Subject to modifications resulting from technical improvements!
57
5.3.16 Replacing the hot surface ignitor
Disconnect the system from the power supply.
Disconnect the plug-in cable.
Loosen fixing screws and remove hot surface ignitor.
Fit new hot surface ignitor and retighten fixing
screws.
Plug in cable connection.
Connect system to mains power supply.
5.3.17 Checking the hose connection between the gas-air
injector and gas-valve assembly
Check hose connection for tightness and for signs of
possible blockages or damage.
Check that the hoses are correctly fitted to P1.
Hose connection:
P1 + , to T-piece gas-valve assembly.
fig. 77 Replacing the hot surface ignitor
fig. 78 Checking the hose connection between the gas-air
injector and gas-valve assembly (Honeywell gas
units)