5.3.24 Checking the three-way valve for correct
activation
Set the mains switch to “0”.
Push in catch on regulating motor and remove bayo-
net connector by twisting anticlockwise (fig. 85).
Remove regulating motor.
Set the mains switch to “I” and press the “reset” but-
ton.
Once the 800 Series is in operation, open one of the
hot-water taps. If the regulating motor starts up
(check for movement of red adjusting lever), the acti-
vation system of the three-way valve is in order.
Shut the hot-water tap.
Set the mains switch to “0”.
If the activation system of the three-way valve is in or-
der, attach the regulating motor and lock into place
by twisting the bayonet connector.
5.3.25 Replacing the control valve
Close maintenance isolating valves and drain the
800 Series.
Remove the control valve with a spanner and fit a
new unit.
Fit regulating motor and lock into place by twisting
the bayonet connector.
Plug cable in.
fig. 85 Checking the three-way valve for correct activation
fig. 86 Replacing the valve core on the 800 –
24/24T25/29/43/60
NOTE
Open the maintenance isolating valves and
then fill the 800 Series and purge the
system of air.