Diagnosis6
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!
30
6 Diagnosis
section 30 Diagnosis
You can find a further explanation of the diagnosis in section 6, chapter 1 on page 6.
section 31
No indication on the display of the BC10 (section 1, [4]).
Step 1 Does the boiler work normally? Yes: Step 2
No:
Step 11
Step 2. Check that there is 7.8 to 15.2 VDC on both contacts 1 and 2 of the connector between the BC10 and the bottom
plate of the BC10, see section 124 and section 131.
Step 3 Is there a voltage? Yes:
Step 4
No: Step 8
Step 4 Check the contact between the BC10 (section 1,[4]) and its slot by pushing on the BC10.
Step 5 Is there any indication on the BC10 display within a few minutes? Yes:
Step 6
No:
Step 7
Step 6 Diagnosis: There is insufficient contact between the BC10 (section 1, [4]) and its slot.
Action: replace BC10 and/or its slot.
Section 67
Step 7 Diagnosis: The control panel BC10 is out of order.
Action: Replace BC10. See the Installation and servicing instructions of the BC10.
Section 67
Step 8 Check the corresponding component of the wire harness, see section 131.
Step 9 Is the wire harness free of damage? Yes:
Section 66
No:
Step 10
Step 10 Diagnosis: The wire harness is defective. Action: Replace the wire harness or the affected part. Section 67
Step 11 Check that the plug is in the grounded socket.
Step 12 Is the plug in the grounded socket? Yes:
Step 14
No: Step 13
Step 13 Diagnosis: The plug is not in the grounded socket.
Action: Insert the plug into the grounded socket, see section 79.
Section 67
Step 14 Check that the main power switch is in position "1" as indicated in section 80.
Step 15 Is the main power switch in position “1” (On)? Yes:
Step 17
No:
Step 16
Step 16 Diagnosis: The main power switch is not in position“1” (On).
Action: Turn the main power switch in position "1" (ON), see section 80.
Section 67
Step 17 Is there 120 VAC on the grounded socket?
Step 18 Is there 120 VAC on the grounded socket? Yes:
Step 20
No:
Step 19
Step 19 Diagnosis: There is not 120 VAC on the grounded socket.
Action: Remedy the problem in the electrical system.
Section 67
Step 20 Measure the resistance of the 120 VAC power supply cable.
Step 21 Is the resistance of the 120 VAC power supply cable within the specified limits? Yes:
Step 23
No:
Step 22
Step 22 Diagnosis: The wire harness is defective. Action: Replace the wire harness or the affected part.
Section 67
Step 23 Test the fuse on the rear of the UBA 3 using a multimeter, see section 82.
Step 24 Is the fuse working correctly? Yes:
Section 66
No:
Step 25