Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!
87
section 123 Checking the wire harness;
connections
Switch off the power supply to the heating system, see
section 72.
Open the boiler door as instructed in section 73.
Remove the UBA 3 as instructed in section 82.
Remove the cover from the connection tray, see section 114.
Set the multimeter to "Measure resistance" [1].
Check the electrical resistance of the connection between the
two black contacts (low-voltage connector pins 22 and 24) on
the UBA 3 mounting base [2]. The electrical resistance of this
connection must be approximately 0
Ω [2].
Check the electrical resistance of the connection between the
two black contacts (low-voltage connector pins 50 and 78) on
the UBA 3 mounting base [2]. The electrical resistance of this
connection must be approximately 0
Ω [2].
Install the lid on the connection tray in reverse order.
Install the UBA 3 in reverse order of removal.
Close the boiler door as instructed in section 77.
Switch on the power supply to the heating system, see
section 79.
1
2
81-pin low-voltage connector
16-pin high-voltage connector
section 124 Checking the cotrol panel;
supply voltage
Open the cover of the BC10 on the front of the boiler as
instructed in section 69.
Remove the BC10 by depressing the lock on the left-hand
side.
Switch on the power supply to the heating system, see
section 79.
Put the main power switch on the control panel in position "1"
(On), see section 80.
Set the multimeter to "Measure DC voltage".
Check that there is between 7.8 and 15.2 VDC on both left-
hand contacts of the connector on the bottom plate of the
BC10.
Install the BC10 in reverse order.
Close the cover of the BC10 on the front of the boiler in
reverse order.