Installation and wiring
Type 8045
flow direction
50 x DN 5 x DN
40 x DN 5 x DN
25 x DN 5 x DN 20 x DN
18 x DN 5 x DN 15 x DN 5 x DN
With control valve Pipe with 2 elbows at 90° in 3
dimensions
Pipe with 2 elbows at 90° Pipe with 1 elbow at 90° or 1
T-piece
With pipe expansion With pipe reduction
Fig. 4 : Upstream and downstream distances depending on the
design of the pipes.
→ Respect the following additional mounting conditions to ensure
that the measuring device operates correctly:
Protect this device against electromagnetic interference,
ultraviolet rays and, when installed outdoors, the effects of
the climatic conditions.
7.2. Recommandations for installing
the 8045 on the pipe
→ Choose an S020 fitting appropriate to the velocity of the fluid
inside the pipe.
→ Install the device on the pipe in such a way that the upstream and
downstream distances are respected according to the design of
the pipes, refer to standard EN ISO 5167-1 and Fig. 4: