EasyManua.ls Logo

Burnham FREEDOM - Page 17

Burnham FREEDOM
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17
TABLE 7.5: PERMISSIBLE STAINLESS STEEL VENT SYSTEMS AND
PRINCIPLE VENT COMPONENTS (VENT OPTIONS 2, 5)
MANUFACTURER VENTSYSTEM SIZE COMPONENT PARTNUMBER
HEATFAB
SAF-TVENT
EZSEAL
3 BOILER
COLLAR 101004-01
3 WALLTHIMBLE HEATFAB7393,7393GCS,5391CI
3 HORIZONTALTERMINAL 8110701
3 VERTICALTERMINAL HEATFAB9392
PROTECH
SYSTEMS
INC.
FASNSEAL
3 BOILER
COLLAR 101004-01
3 W
ALLTHIMBLE FSWT3
3 HORIZONTALTERMINAL 8110701
3 VERTICALTERMINAL FSBS3
Z-FLEX
SVE
SERIES
III
(“Z-VENTIII”)
3 BOILER
COLLAR 101004-01
3 W
ALLTHIMBLE 2SVSWTEF03
3 HORIZONT
ALTERMINAL 8110701
3 VERTICALTERMINAL 24SVSTPF03
METAL-FAB CORR/GUARD
3 BOILERCOLLAR 101004-01
3 WALLTHIMBLE CGSWWPK(3")
3 HORIZONTALTERMINAL 8110701
3 VERTICALTERMINAL CGSWHTM(3")
NOTES:
1) Seeventsystemmanufacturersliteratureforotherpartnumbersthatarerequiredsuchasstraight
pipe,elbows,restopsandventsupports.
2) PartNo.101004-01collarreplacesfactory-mountedconcentriccollar(Figure7.16).
6)PermittedTerminalsforVerticalVenting -
Vent Option 5-Astraightterminationisinstalledintheendoftheventpipe.Ventmanufacturerpartnumbersforthese
screensareshowninTable7.5.Theairinletterminalconsistsofa180degreeelbow(ortwo90degreeelbows)witha
rodentscreenasshowninFigure7.10
Vent Option 6-UseU.S.Boilerpart101495-01withtheappropriateashing(seeTable7.4b).
7)VerticalVentTerminalLocations(VentOptions5,6)-Observethefollowinglimitationsonthelocationofallverticalvent
terminals(seeFigures7.10and7.11):
• Thetopoftheventpipemustbeatleast2feetaboveanyobjectlocatedwithin10feet.
• ForVentOption#5,theverticaldistancebetweentopoftheventandairinletterminalopeningsmustbeatleast12".
• Thebottomoftheairinletterminalmustbeatleast12”abovethenormalsnowaccumulationthatcanbeexpectedon
theroof.TheterminalusedinVentOption#6hasaxeddistanceabovethestormcollarof19".Ifagreaterdistance
isneededtoprovidetheclearanceabovethesnowline,buildachaseontheroofandmounttheverticalterminalontop
ofthechase.
• ForVentOption#5,theairintaketerminalmustbelocatedontheroofandmustbenofurtherthan24"horizontally
fromtheexhaustpipe.
8) Wallthimbles–Wallthimblesarerequiredwheresinglewallventpipepassesthroughcombustiblewallswithlessthan
therequiredclearanceshowninTable4.2orasrequiredbylocalcodes.Stainlessventmanufacturerswallthimblepart
numbersareshowninTable7.5.Notethatconcentricventhasa"zero"clearancetocombustiblesandthereforedoesnot
requiretheuseofwallthimbles.

Other manuals for Burnham FREEDOM

Related product manuals