Scheduled Maintenance
Table 6 details the preventive maintenance schedules of the C65 Hybrid UPS systems
under normal environmental conditions. This information is provided for your reference.
Only Authorized Service Providers are permitted to access MicroTurbine components and
perform these maintenance tasks.
Table 6. C65 Hybrid UPS package Gaseous Fuels
Maintenance
Interval
3
Component
Maintenance
Action
Comments
24 months UCB Battery Replace
5 years
Electronic
Components: ECM,
LCM & BCM Power
Boards, BCM & ECM
Fan Filters, Fans, EMI
Filter, Frame PM
Replace
Per Mfg
Instructions
External Energy
Storage
Replace
Refer to manufacturer’s requirements for the
energy storage system being used
4,000 hours
Engine Air Filter Inspect Replace if required - see Note 1
Electronics Air Filter Inspect Clean if necessary - see Note 1
Fuel Filter Element
(External)
Inspect Replace if required - see Note 1
Fuel System Leak Check
Refer to "Gaseous Fuel Fittings and
Components" section below for
recommended procedure
8,000 hours
Engine Air Filter Replace See Note 1
Electronics Air Filter Clean
Fuel Filter Element
(External)
Replace See Note 1
Igniter Replace See Note 2
ICHP Actuator Replace
20,000 hours
Injector Assemblies Replace
TET Thermocouple Replace
40,000 hours Engine Replace Use Reman or New Engine Replacement
NOTE 1
Filters may require more frequent attention based upon environment,
installation, and/or air/fuel quality. Inspect new installations frequently to
determine best inspection/ replacement periods for air and fuel filters.
NOTE 2
Load profiles with frequent onloads and offloads may require more frequent
igniter replacement due to igniter operation during injector switching.
NOTE 3
Months and Years are elapsed time. Hours are “Engine Hours,” as recorded by
each Hybrid UPS system.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Capstone MicroTurbine C65 and is the answer not in the manual?

Capstone MicroTurbine C65 Specifications

General IconGeneral
BrandCapstone
ModelMicroTurbine C65
CategoryUPS
LanguageEnglish