Output
Aux Out Type Auxiliary output type sets the use for the 24VAC auxiliary output signal. If a
powered exhaust is selected for this output, it will eliminate the option to control a powered
exhaust with a 0-10VDC signal.
VDC Out1 Output #1 configures the use for OUT #1 on the “To RTU” side of the RTULink.
VDC Out2 Output #2 configures the use for OUT #2 on the “To RTU” side of the RTULink.
VDC Out1 Range Output 1 range is the voltage range that the component connected to output
1 is designed to operate with. Once set, the RTULink will use the low-end voltage of this range
for an OFF signal and the high-end voltage of this range for a fully modulated ON signal.
VDC Out2 Range Output 2 range is the voltage range that the component connected to output
1 is designed to operate with. Once set, the RTULink will use the low-end voltage of this range
for an OFF signal and the high-end voltage of this range for a fully modulated ON signal.
Power Exhaust The powered exhaust threshold is the percentage open the economizer/damper must
be in order for the powered exhaust to turn on. For an ON/OFF powered exhaust, this is the threshold at
which it turns on. For a modulating powered exhaust, the speed of the exhaust will modulate linearly as
the economizer/damper opens from this threshold to fully open (100% open).
Enable Max HP Setting to enable or disable maximum heat pump runtime.
Max HP Runtime Time setting for heat pump runtime before auxiliary heat activates
Emer. Heat Lock Setting to enable or disable emergency heat.
Lockout Temp If the outside air temperature is above “Lockout Temp” setting, emergency heat will be
locked out.
Set Point Limit Setting to enable set point limit adjustments.
Limit SP Adjust This allows the user to change the current temperature set point through the home screen.
The range adjustment is 0-100 degrees.
Service
Password to enter factory menu is 1 2 3 4.
Temperatures User can monitor various temperature values.
Air % Displays outdoor and return air percentage.
RH Values User can monitor various RH values.
Open/Closed Status Menu to view the open/closed status of all inputs.
Inputs Allows user to monitor all of the variable input values.
Outputs Allows user to monitor all of the variable output values.
Clear Faults This will clear the entire fault history. If there is an active fault when cleared, that fault will show up
until it is fixed.
Set Clock Set day and time.
Time Zone Set time zone for the unit.
Factory Reset This will reset the board to factory commissioned settings.