23
ENG
clima +030220641 - rel. 1.0 - 07.12.2007
Con guration 1 (AdC =1) - DiP 4 has no e ect
The typical application is the control of a classic system with air-
conditioner + boiler and humidity control using a CAREL proportional
humidi er, for example the compactSteam series. Dehumidi cation is
performed using the air-conditioner, making sure that the temperature
conditions are within the comfort limits.
There are two humidity set points, one for humidi cation and the other for
dehumidi cation; the changeover points for automatic humidi cation/
dehumidi cation operation are also de ned.
There is just one temperature set point for both cooling and heating, the
changeover (cooling/heating) occurs based on the activation points of
the two outputs.
Dehumidi cation can only be activated if the humidity exceeds the
dehumidi cation set point plus the di erential dFd, and furthermore:
Temp > Set – dS1 – dF2
It is deactivated if the humidity is below the dehumidi cation set point
and in furthermore:
Temp < Set – dS1 – dF2 – 0.5 °C
See the following graph for the description of this operating mode.
dS1dF2 dIF
dS1
Output
Output Output
Set point temperatura inverno/estate
Temp.
%U.R.
dFH
dSA
% U.R
10 V
0 V
Set point umidifica Set point deumidifica
dFd
R2 R2
R1
Fig. 5.m
Parameters involved:
Code Description Default LE
Value or
link if LE
= 1
- day set point (same) 20.0 °C 1 -
night set point (same) 18.0 °C 1 -
dIF relay 1 di erential 1.0 °C 1 -
dF2 relay 2 di erential 1.0 °C 2 = dIF
dS1 relay o set 0.5 °C 1 -
dSA analogue output o set 0 % rH 2 =0
humidi cation set point 50.0 % rH 1 -
dehumidi cation set point 70.0 % rH 1 -
dFH humidi cation di erential 5.0 % rH 1 -
dFd dehumidi cation di erential 5.0 % rH 1 -
Tab. 5.i
Con guration 2 (AdC = 2) - DiP 4 has no e ect
For the control of a classic reverse-cycle air-conditioning system, with
automatic cooling/heating changeover and proportional humidity
control using the CAREL compactSteam humidi er.
Automatic operating mode is signalled on the display by the AUTO
symbol, next to the set point.
There are two set points, one for cooling and the other for heating, and
both can be set.
The mode switches between cooling and heating automatically
according to the room temperature measured.
The two set points are set by pressing the SET button or the UP or DOWN
button, rst the cooling set point is displayed and then the heating set
point, the controller automatically checks that there is a di erence of at
least 1°C between the two set points.
Relay 1 controls the heating/cooling signal.
The analogue output controls humidi cation.
Relay output 2 manages the changeover in mode.
See the following graph for the description of this operating mode.
dFH
10 V
0 V
dSA
% U.R
Output
Set point umidica
dS1dF2 dIFdS1
Temp. Temp.
Output Output
Set point estateSet point inverno
R1 R1
R2
Fig. 5.n
Parameters involved:
Code Description Default LE
Value or
link if LE
= 1
day set point in cooling 24.0 °C 1 -
night set point in cooling 26.0 °C 1 -
day set point in heating 20.0 °C 1 -
night set point in heating 18.0 °C 1 -
dIF relay 1 di . in cooling mode 1.0 °C 1 -
dF2 relay 1 di . in heating mode 1.0 °C 2 = dIF
dS1 relay 1 o set 0.5 °C 2 = 0
dSA analogue output o set 0 % rH 2 = 0
humidi cation set point 50.0 % rH 1 -
dFH analogue output di erential 5.0 % rH 1
Tab. 5.j