6. TABLE OF PARAMETERS
6.1 Description of the parameters for the
standard version
The parameters available depend on the clima model used and the level
set (LE = 1 or 2)
code parameter range default UOM note
day temperature set point in cooling 10 to 50 24.0 °C
night temperature set point in cooling 10 to 50 26.0 °C
day temperature set point in heating 10 to 50 20.0 °C
night temperature set point in heating 10 to 50 18.0 °C
single day temperature set point for automatic modes 10 to 50 20.0 °C
single night temperature set point for automatic modes 10 to 50 18.0 °C
dIF
Temperature di erential for relay 1
This is an absolute value and is added to or subtracted from the set point depending on the control
mode, cooling or heating.
0.1 to 10 1.0 °C
dF2
Temperature di erential for relay 2.
This is an absolute value and is added to or subtracted from the set point depending on the control
mode, cooling or heating.
0.1 to 10 1.0 °C
dS1
Temperature o set for relay 1
This value is added to or subtracted from the set point based on the active control mode. May be positive
or negative, so as to o er complete  exibility in the position of the step.
-10 to 10 0.5 °C
dFA
Analogue output di erential
This value is added to or subtracted from the set point according to the control mode selected, cooling or
heating,.
0 to 10 1.0 °C
dSA
Analogue output o set from to the set point
This value is added to or subtracted from to the set point according to the operating mode, cooling or
heating.
-10 to 10 0.0
°C/
% rH
EHI
Maximum water temperature for ON/OFF radiant  oor heating control (mode 8, all dipswitches o ). The
screen shows alarm EHI and the relay output is deactivated, irrespective of the control mode..
10 to 80 40 °C
ELo
Minimum water temperature for ON/OFF radiant  oor cooling control (mode 8, all dipswitches o ). The
screen shows alarm ELo and the relay output is deactivated, irrespective of the control mode.
0 to 50 10 °C
Humidi cation set point 10 to 70 50.0 % rH
Dehumidi cation set point 10 to 70 70.0 % rH
dFH
Humidity di erential for the activation of the analogue output and the relay. 1 to 20 5.0 % rH
dFd
Dehumidi cation di erential for the activation of the relay. 1 to 20 5.0 % rH
SFH
Parameter to de ne the humidi cation/dehumidi cation status in day and night mode
Activates or deactivates humidi cation or dehumidi cation control (based on DIP 4) with the time bands.
The parameter can have the following three values
0 - Time bands disabled.
The humidi cation/dehumidi cation control is always active, if featured, and is con gured in relation to
dip4
1 - Time bands enabled:
When switching to the daytime band, humidi cation/dehumidi cation control (depends on dip4) is
activated.
When switching to the night band, humidi cation/dehumidi cation control (depends on dip4) is
deactivated.
2 - Time bands enabled:
When switching to the daytime band, humidi cation/dehumidi cation control (depends on dip4) is
deactivated.
When switching to the night band, humidi cation/dehumidi cation control (depends on dip4) is
activated.
0 to 2 0 -
AUt
Humidity set point automatically compensated by the outside temperature
If humidity control is featured, the ambient humidity is controlled with an automatic set point, de ned
from 1H to 7H using the buttons, as speci ed in the corresponding table (see page 15).
If set to OFF the mode is disabled.
Setting one of the levels in the table, the controller independently sets a humidity set point in relation to
the outside temperature.
OFF
1H to 7H
OFF -