“EVD Evolution TWIN” +0300006EN - rel. 2.6 - 31.01.2019
18
Valve
Setting the type of valve automatically denes all the control parameters based
on the manufacturer’s data for each model. In Manufacturer programming
mode, the control parameters can then be fully customised if the valve used is
not in the standard list. In this case, the controller will detect the modication
and indicate the type of valve as “Customised”.
Parameter/description Def.
CONFIGURATION
Valve:
0= user dened; 1= CAREL ExV; 2= Alco EX4; 3=Alco EX5; 4=Alco
EX6; 5=Alco EX7; 6=Alco EX8 330 Hz recommended CAREL;
7=Alco EX8 500 Hz specic Alco; 8=Sporlan SEI 0.5-11; 9=Sporlan
SER 1.5-20; 10=Sporlan SEI 30; 11=Sporlan SEI 50; 12=Sporlan
SEH 100; 13=Sporlan SEH 175; 14=Danfoss ETS 12.5-25B;
15=Danfoss ETS 50B; 16=Danfoss ETS 100B; 17=Danfoss ETS 250;
18=Danfoss ETS 400; 19=Two EXV CAREL connected together;
20=Sporlan SER(I)G,J,K; 21= Danfoss CCM 10-20-30; 22= Danfoss
CCM 40; 23=Danfoss CCMT 2-4-8; 24 = Disabled
CAREL
E
X
V
Tab. 4.c
Note: select Valve = disabled if Main control = I/O expansion for pCO
to prevent the EEV motor error from being displayed. I/O expansion for pCO
control can be selected at the end of the commissioning procedure, by
entering programming mode.
Important:
• two CAREL EXV valves connected together must be selected if two
CAREL EXV valves are connected to the same terminal, to have parallel or
complementary operation;
• as described, control is only possible with CAREL EXV valves;
• NOT all CAREL valves can be connected: see paragraph 2.5.
Pressure/refrigerant level probe S1 & S3
Setting the type of pressure probe S1 for driver A and S3 for driver B denes
the range of measurement and the alarm limits based on the manufacturer’s
data for each model, usually indicated on the rating plate on the probe.
Select “CAREL liquid level” and connect the CAREL oat level sensor to manage
the following functions:
- evaporator liquid level control with CAREL sensor;
- condenser liquid level control with CAREL sensor.
For example, connecting two CAREL liquid level probes, one to S1 and one to
S3, allows independent control of two refrigerant liquid levels.
See the chapter on “Control”.
Parameter/description Def.
CONFIGURATION
Probe S1, S3 Ratiom.:
-1 to 9.3
barg
Ratiometric (OUT= 0 to 5 V) Electronic (OUT= 4 to 20 mA)
1= -1 to 4.2 barg 8= -0.5 to 7 barg
2=-0.4…9.3 barg 9= 0 to 10 barg
3= -1 to 9.3 barg 10= 0 to 18.2 barg
4= 0 to 17.3 barg 11= 0 to 25 barg
5= 0.85 to 34.2 barg 12= 0 to 30 barg
6= 0 to 34.5 barg 13= 0 to 44.8 barg
7= 0 to 45 barg 14= remote, -0.5 to 7 barg
15= remote, 0 to 10 barg
16= remote, 0 to 18.2 barg
17= remote, 0 to 25 barg
18= remote, 0 to 30 barg
19= remote, 0 to 44.8 barg
20= External signal (4 to 20 mA)
21= -1 to 12.8 barg
22= 0 to 20.7 barg
23= 1.86 to 43.0 barg
24 = CAREL liquid level
25 = 0...60,0 barg
26 = 0...90,0 barg
27 = external signal (0 to 5 V)(*)
Tab. 4.d
(*) for programmable positioner. See chapter “Control”.
Important: if two pressure probes S1 and S3 are installed, these must
be the same type. A ratiometric probe and an electronic probe cannot be
used together.
Note: in the case of multiplexed systems where the same pressure
probe is shared between the twin1 and twin2 controllers, choose the normal
option for driver A and the “remote” option for the remaining drivers.
Example: to use the same pressure probe P1 for driver A and B: 4 to 20 mA,
-0.5 to 7 barg
For driver A on the twin 1 controller select: 4 to 20 mA, -0.5 to 7 barg.
For driver B on the twin 1 controller and for driver A and B on the twin 2
controller select: remote 4 to 20 mA, -0.5 to 7 barg.
The connection diagram is shown in paragraph 2.6
Note:
• the range of measurement by default is always in bar gauge (barg). In
the manufacturer menu, the parameters corresponding to the range of
measurement and the alarms can be customised if the probe used is not
in the standard list. If modifying the range of measurement, the controller
will detect the modication and indicate the type of probe S1 or S3 as
“Customised”;
• the software on the controller takes into consideration the unit of measure.
If a range of measurement is selected and then the unit of measure is
changed (from bars to psi), the controller automatically updates the limits
of the range of measurement and the alarm limits. By default, the main
control probes S2 and S4 are set as “CAREL NTC”. Other types of probes can
be selected in the service menu;
• unlike the pressure probes, the temperature probes do not have any
modiable parameters relating to the range of measurement, and
consequently only the models indicated in the list can be used (see
the chapter on “Functions” and the list of parameters). In any case, in
manufacturer programming mode, the limits for the probe alarm signal
can be customised.
Main control
Setting the main control denes the operating mode for each driver.
Parameter/description Def.
CONFIGURATION
Main control
Superheat control
1= multiplexed showcase/cold room multiplexed
showcase/
cold room
2= showcase/cold room with compressor on board
3= “perturbed” showcase/cold room
4= showcase/cold room with sub-critical CO
2
5= R404A condenser for sub-critical CO
2
6= air-conditioner/chiller with plate heat exchanger
7= air-conditioner/chiller with tube bundle heat exchanger
8= air-conditioner/chiller with nned coil heat exchanger
9= air-conditioner/chiller with variable cooling capacity
10= “perturbed” air-conditioner/chiller
Special control
11= EPR back pressure
12= hot gas bypass by pressure
13= hot gas bypass by temperature
14= transcritical CO
2
gas cooler
15= analogue positioner (4 to 20 mA)
16= analogue positioner (0 to 10 V)
17= air-conditioner/chiller or showcase/cold room with
adaptive control
18= air-conditioner/chiller with Digital Scroll compressor (*)
19=AC/chiller with BLDC scroll compressor
(CANNOT BE SELECTED)
20=superheat regulation with 2 temperature probes
(CANNOT BE SELECTED)
21=I/O expander for pCO
22= Programmable SH regulation
23= Programmable special regulation
24= Programmable positioner
25= Evaporator liquid level regulation with CAREL sensor
26= Condenser liquid level regulation with CAREL sensor
(*) only for CAREL valves controls
Tab. 4.e