EasyManua.ls Logo

Carel EVD Evolution Twin - Page 43

Carel EVD Evolution Twin
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ENG
“EVD Evolution TWIN” +0300006EN - rel. 2.6 - 31.01.2019
43
user *
Parameter/description Def. Min. Max. UOM
Type **
CAREL SVP
Modbus®
Note
A Main control:
1= Multiplexed showcase/cold room
2= Showcase/cold room with compressor on board
3= “Perturbed” showcase/cold room
4= Showcase/cold room with
sub-critical CO
2
5= R404A condenser for sub-critical
CO
2
6= Air-conditioner/chiller with plate heat exchanger
7= Air-conditioner/chiller with tube bundle heat exchanger
8= Air-conditioner/chiller with nned coil heat exchanger
9= Air-conditioner/chiller with variable cooling capacity
10= “Perturbed” air-conditioner/chiller
11= EPR back pressure
12= Hot gas bypass by pressure
13= Hot gas bypass by temperature
14= Transcritical
CO
2
gas cooler
15= Analogue positioner (4 to 20 mA)
16= Analogue positioner (0 to 10 V)
17= Air-conditioner/chiller or showcase/cold room with adaptive control
18= Air-conditioner/chiller with Digital Scroll compressor (*)
19= AC or chiller with BLDC scroll compressor (CANNOT BE SELECTED)
20= superheat regulation with 2 temperature probes (CANNOT BE
SELECTED)
21= I/O expander for pCO (**)
22= Programmable SH regulation
23= Programmable special regulation
24= Programmable positioner
25= Evaporator liquid level regulation with CAREL sensor
26= Condenser liquid level regulation with CAREL sensor
(*)= control only settable on driver A, however corresponds to the
entire controller
Multiplexed
showcase/
cold room
- - - I 56 183 -
A Probe S2:
0= user dened
1= CAREL NTC
2= CAREL NTC-HT high temp.
3= combined NTC SPKP**T0
4= 0 to 10V external signal
5= NTC – LT CAREL low temperature
CAREL NTC - - - I 17 144 CO
A Auxiliary control:
0=
user dened
1= Disabled
2= high condensing temperature protection on S3 probe
3= modulating thermostat on S4 probe
4= backup probes on S3 and S4
5, 6, 7 = Reserved
8= Subcooling measurement
9= Inverse high condensation temperature protection on S3 probe
10= Reserved
----I18145CO
A Probe S3:
0= User dened;
Ratiometric (OUT=0 to 5 V) Electronic (OUT=4 - 20 mA)
1= -1 to 4.2 barg 8= -0.5 to 7 barg
2= 0.4 to 9.3 barg 9= 0 to 10 barg
3= -1 to 9.3 barg 10= 0 to 18.2 bar
4= 0 to 17.3 barg 11= 0 to 25 barg
5= 0.85 to 34.2 barg 12= 0 to 30 barg
6= 0 to 34.5 barg 13= 0 to 44.8 barg
7= 0 to 45 barg 14= remote, -0.5 to 7 barg
15= remote, 0 to 10 barg
16= remote, 0 to 18.2 barg
17= remote, 0 to 25 barg
18= remote, 0 to 30 barg
19= remote, 0 to 44.8 barg
20= 4 to 20mA external signal
21= -1 to 12.8 barg
22= 0 to 20.7 barg
23= 1.86 to 43.0 barg
24= CAREL liquid level
25 = 0...60,0 barg
26 = 0...90,0 barg
27 = external signal 0…5 V
Ratiometric:
-1 to 9.3 barg
---I19146CO

Table of Contents

Related product manuals