“EVD Evolution TWIN” +0300006EN - rel. 2.6 - 31.01.2019
45
user *
Parameter/description Def. Min. Max. UOM
Type **
CAREL SVP
Modbus®
Note
A DI1 conguration
1= Disabled
2= Valve regulation optimization after defrost
3= Discharged battery alarm management
4= Valve forced open (at 100%)
5= Regulation start/stop
6= Regulation backup
7= Regulation security
Regulation
start/stop
(tLAN-RS485)
/ Regulation
backup
(pLAN)
---I85212CO
C Language: Italiano; English Italiano - - - - - - CO
C Auxiliary refrigerant
-1=
User dened; 0 = same as main regulation
1= R22 2= R134a 3= R404A 4= R407C 5= R410A
6= R507A 7= R290 8= R600 9= R600a 10= R717
11= R744 12= R728 13= R1270 14= R417A 15= R422D
16= R413A 17= R422A 18= R423A 19= R407A 20= R427A
21= R245FA 22= R407F
23=R32 24=HTR01 25= HTR02
26=R23 27 = R1234yf 28 = R1234ze 29 = R455A 30 = R170
31 = R442A 32 = R447A 33 = R448A 34 = R449A 35 = R450A
36 = R452A 37 = R508B 38 = R452B 39 = R513A 40 = R454B
41 = R458A
R404A - - - I 96 223 CO
PROBES
C S1: calibration oset 0 -60(-870), -60 60(870), 60 barg (psig)
mA
A3433 CO
C S1: calibration gain, 4 to 20 mA 1 -20 20 - A 36 35 CO
C Pressure S1: MINIMUM value -1 -20 (-290) Pressure S1:
MAXIMUM
value
barg (psig) A 32 31 CO
C Pressure S1: MAXIMUM value 9.3 Pressure S1:
MINIMUM
value
200 (2900) barg (psig) A 30 29 CO
C Pressure S1: MINIMUM alarm value -1 -20 (-290) Pressure S1:
MAXIMUM
alarm value
barg (psig) A 39 38 CO
C Pressure S1: MAXIMUM alarm value 9.3 Pressure S1:
MINIMUM
alarm value
200 (2900) barg (psig) A 37 36 CO
C S2: calibration oset 0 -20 (-36), -20 20 (36), 20 °C (°F), volt A 41 40 CO
C S2: calibration gain, 0 to 10 V 1 -20 20 - A 43 42 CO
C Temperature S2: MINIMUM alarm value -50 -85(-121) Temperature
S2: MAXIMUM
alarm value
°C (°F) A 46 45 CO
C Temperature S2: MAXIMUM alarm value 105 Temperature
S2: MINIMUM
alarm value
200 (392) °C (°F) A 44 43 CO
C S3: calibration oset 0 -60 (-870) 60 (870) barg (psig) A 35 34 CO
C S3: calibration gain, 4 to 20 mA 1 -20 20 - A 82 81 CO
C Pressure S3 : MINIMUM value -1 -20 (-290) Pressure S3:
MAXIMUM
value
barg (psig) A 33 32 CO
C Pressure S3: MAXIMUM value 9.3 Pressure S3:
MINIMUM
value
200 (2900) barg (psig) A 31 30 CO
C Pressure S3: MINIMUM alarm value -1 -20 (-290) Pressure S3:
MAXIMUM
alarm value
barg (psig) A 40 39 CO
C Pressure S3: MAXIMUM alarm value 9.3 Pressure S3:
MINIMUM
alarm value
200 (2900) barg (psig) A 38 37 CO
C S4: calibration oset 0 -20 (-36) 20 (36) °C (°F) A 42 41 CO
C Temperature S4: MINIMUM alarm value -50 -85(-121) Temperature
S4: MAXIMUM
alarm value
°C (°F) A 47 46 CO
C Temperature S4: MAXIMUM alarm value 105 Temperature
S4: MINIMUM
alarm value
200 (392) °C (°F) A 45 44 CO
C S1/S3 Maximum dierence (pressure) 0 0 200(2900) bar(psig) A 114 113 CO
C S2/S4 Maximum dierence (temperature) 0 0 180(324) °C (°F) A 115 114 CO
C Alarm delay S1 0 0 240 s I 131 258 CO
C Alarm delay S2 0 0 240 s I 132 259 CO
C Alarm delay S3 0 0 240 s I 133 260 CO
C Alarm delay S4 0 0 240 s I 134 261 CO
C Enable S1 0 0 1 - D 16 15 CO
C Enable S2 0 0 1 - D 17 16 CO
C Enable S3 0 0 1 - D 18
17 CO
C Enable S4 0 0 1 - D 19 18 CO