19
ENG
“heaterSteam” +0300080EN - rel. 1.0 - 27.04.2016
4.3 Control board
The control board (S) is inside of the electrical panel in the wall dividing.
The auxiliary connections (probes, remote terminal, alarm) are made by
inserting the cables form the outside into the electrical panel.
To do this, use cables gland located on the base of the unit to the plug-in
screw terminals on the control board.
UR002-UR013 UR020-UR080
6
6
Fig. 4.i Fig. 4.j
M2M9
12 1 123 123452121122123456
J17C
2 1
J17L J23 J24 J19J20J3 J16 M3 J18
2 1
J21
M8 M1 M5 M6M12
1 1234567821132 31221212
main probe
ext. regulator
GND
GND
Remote
ON/OFF
limit probe
12Vdc
Control signal
Ethernet
GND
RS485 Serial
L+
L-
Alarm
relay
NO
NC
C
NO
C
Unit
status
relay
Fig. 4.k
Key:
Terminal Function Electrical specifi cations
M1 M1.1 GND (G0)
M1.2 Controller power supply 24Vac +10%/-15% 50/60Hz
M2 M2.1 Main room probe signal
input or signal from external
controller
0/1V, 0/10V, 2/10V, 0/20mA,
4/20mA, NTC 10 kΩ a 25 °C
M2.2 GND
M2.3
Probe power supply (+G)
+12 Vdc, maximum current that
can be delivered 50 mA; Protec-
tion against short-circuits
M2.4
Digital input for backup/
rotation function
Maximum current output: 5 mA;
Maximum voltage with contact
open: 13 Vdc
M2.5 Limit humidity probe signal
input
0/1V, 0/10V, 2/10V, 0/20mA,
4/20mA, NTC
M2.6 GND
M2.7 GND
M2.8
Remote on/off contact
digital input
Maximum current output: 5 mA;
Maximum voltage with contact
open: 13 Vdc
M3 M3.1
Fieldbus
Tx/Rx-
M3.2 Tx/Rx+
M3.3 GND
M5 M5.1 Unit status contact (NO)
250 Vac; 2 A with resistive load;
2 A with inductive load
M5.2 Unit status contact
common
M6 M6.1 Alarm common
250 Vac; 2 A with resistive load;
2 A with inductive load
M6.2 NC alarm contact
M6.3 NO alarm contact
Terminal Function Electrical specifi cations
M8 M8.1 Production request analo-
gue output
Output voltage range: 0-10 V
max 10 mA
M8.2 GND
M9 M9.1 Backup and rotation contact
common
250 Vac; 2 A with resistive load;
2 A with inductive load
M9.2 Backup and rotation NO
contact
M11 Ethernet port
M12 M12.1
BMS 485
Tx/Rx-
M12.2 Tx/Rx+
M12.3 GND
Earth connection
J18 pLAN/display terminal
J19 J19.1 Auxiliary/blower contact
(NO)
250 Vac; 2 A with resistive load;
2 A with inductive load
J19.2 Auxiliary/blower contact
common
USB Port (type A)
Ethernet RJ45 Port
Tab. 4.b