23
ENG
“heaterSteam” +0300080EN - rel. 1.0 - 27.04.2016
CONTROL WITH TWO HUMIDITY PROBES
• short-circuit terminals M2.7 – M2.8 (jumper) to enable production;
alternatively connect terminals M2.7 – M2.8 to a remote contact (e.g.:
switch, timer,...);
• connect the main active room probe to terminals M2.1, M2.2 (GND)
and M2.3 (+12Vdc);
• connect the second active probe to terminals M2.5, M2.3 (+12Vdc) and
M2.6 (GND);
• to enable control, set:
Screen ind. Screen desc. Parameter
Ea01 Control type Modulation with two humidity probes
Ea02 Control with 2 probes Set the weight of the two probes (0-100%)
Ea05 Modulating control Set:
humidity set point (0-100 %rH)
diff erential (2-20%rh)
Minimum production (0-100%)
Maximum production (0-100%)
Ec01 Main probe type Select from: 0-1V, 0-10V, 2-10V, 0-20mA, 4-20mA
Ec02 Second probe type Select from: 0-1V, 0-10V, 2-10V, 0-20mA, 4-20mA
The controller will calculate the weighted average between the two
probes. The weight of the two probes can also be set.
M2M9 M8
1 12345678212
OUT H / T
M
+ (G)
Main probe
OUT H / T
M
+ (G)
Second probe
Fig. 4.w
The following probes can be connected:
CAREL probes for rooms DPWC111000
for air ducts DPDC110000; DPDC210000
for technical applications DPPC210000; DPPC210000
Note: non-CAREL active probes can be connected to the controller.
4.7 Control with temperature probes
The controller features independent internal temperature control,
and can be connected to a temperature probe TT (Fig. 4.r). It performs
complete control based on the temperature measured inside the
controlled environment.
TT
Remote
contact
Fig. 4.x
Key:
TT Active temperature probe
Remote Contact Remote contact
CONTROL WITH ONE ACTIVE TEMPERATURE PROBE
• short-circuit terminals M2.7 – M2.8 (jumper) to enable production;
alternatively connect terminals M2.7 – M2.8 to a remote contact (e.g.:
switch, timer,...);
• connect the main active room probe to terminals M2.1, M2.2 (GND)
and M2.3 (+12Vdc);
• to enable control, set:
Screen ind. Screen desc. Parameter
Ea01 Control type one temperature probe
Ea05 Modulating control Set:
temperature set point (0-100 °C) (32-212°F)
diff erential (2-20°C) (3.6-36°F)
Minimum production (0-100%)
Maximum production (0-100%)
Ec01 Main probe type Select from: 0-1V, 0-10V, 2-10V, 0-20mA,
4-20mA
M2M9 M8
1 12345678212
OUT H / T
M
+ (G)
Main probe
Fig. 4.y
_________________________________________________________
CONTROL WITH ONE TEMPERATURE PROBE AND LIMIT PROBE
• short-circuit terminals M2.7 – M2.8 (jumper) to enable production;
alternatively connect terminals M2.7 – M2.8 to a remote contact (e.g.:
switch, timer,...);
• connect the main active room probe to terminals M2.1, M2.2 (GND)
and M2.3 (+12Vdc);
• connect the active limit probe to terminals M2.5, M2.3 (+12Vdc), M2.6 (GND);
• to enable control, set:
Screen ind. Screen desc. Parameter
Ea01 Control type Temperature with limit
Ea05 Modulating
control
Set:
temperature set point (0-100 °C) (32-212°F)
diff erential (2-20°C) (3.6-36°F)
Minimum production (0-100%)
Maximum production (0-100%)
Ea06 Limit probe Set point (0-100 °C/°F)
Diff erential (0-100%)
Ec01 Main probe type Select from: 0-1V, 0-10V, 2-10V, 0-20mA, 4-20mA
Ec02 Limit probe type Select from: 0-1V, 0-10V, 2-10V, 0-20mA, 4-20mA
M2M9 M8
1 12345678212
OUT H / T
M
+ (G)
Main probe
OUT H / T
M
+ (G)
Second probe
Fig. 4.z
The following probes can be connected:
CAREL probes for rooms DPWC111000
for air ducts DPDC110000; DPDC210000
for technical applications DPPC210000, DPPC210000
Note: non-CAREL active probes can be connected to the controller.