30
ENG
“heaterSteam” +0300080EN - rel. 1.0 - 27.04.2016
6.13 Complete programming menu tree
Below is the complete tree of the confi guration menu. Remember that the screen index at the top right on the display
corresponds to the sequence of indices in each menu to reach the specifi c page (see paragraph 4.5 for further details”). There are
two types of menu: Installer and Service.
Menu Screen Menu description Menu type Controller type
A. Clock A01 Set the time, date and time zone Installer
Service
heaterSteam process
heaterSteam titanium
B. Scheduler Scheduler B01 Enable the scheduler (time bands) Installer
Service
heaterSteam process
heaterSteam titanium
B02
(visible if time bands are enabled)
Set the time bands: day, ON time, OFF time
Installer
Service
heaterSteam process
heaterSteam titanium
C. Alarm
thresholds
C01 Set the alarm thresholds
Low humidity/temperature alarm threshold
High humidity/temperature alarm threshold
Limit humidity/temperature alarm threshold
Installer
Service
heaterSteam process
heaterSteam titanium
D. Inputs/outputs Analogue inputs D01 Read values from main probe, limit probe, cylinder water tem-
perature, feedwater conductivity
Installer
Service
heaterSteam process
heaterSteam titanium
Digital inputs D02 Read status of remote On/Off , motor protector, level sensor fl oat
position, foam sensor
Installer
Service
heaterSteam process
heaterSteam titanium
Analogue outputs D03 Read current production Installer
Service
heaterSteam process
heaterSteam titanium
Digital outputs D04 Read status of unit On/Off , contactor, drain pump, fi ll valve, SSR/
fan
Installer
Service
heaterSteam process
heaterSteam titanium
In/Out Wireless probe 1 D05 Read temperature and/or humidity values
Read value of level signal and battery level on probe 1
Installer
Service
heaterSteam process
heaterSteam titanium
In/Out Wireless probe 2 D06 Read temperature and/or humidity values
Read value of level signal and battery level on probe 2
Installer
Service
heaterSteam process
heaterSteam titanium
In/Out Wireless probe 3 D07 Read temperature and/or humidity values
Read value of level signal and battery level on probe 3
Installer
Service
heaterSteam process
heaterSteam titanium
In/Out Wireless probe 4 D08 Read temperature and/or humidity values
Read value of level signal and battery level on probe 4
Installer
Service
heaterSteam process
heaterSteam titanium
E. Settings
(password)
a. Control Control type Ea01 Set the type of control Installer heaterSteam process
heaterSteam titanium
Weights Ea02 Set the weight of the two probes Installer heaterSteam process
heaterSteam titanium
Control proportional to
external signal
Ea03 Sett the hysteresis, minimum production and maximum
production
Installer heaterSteam process
heaterSteam titanium
External ON/OFF Ea04 Set the maximum production with external ON/OFF control Installer heaterSteam process
heaterSteam titanium
Modulating control Ea05 Set the set point, diff erential, min production, max production Installer heaterSteam process
heaterSteam titanium
Limit probe Ea06 Set the set point and diff erential Installer heaterSteam process
heaterSteam titanium
Cylinder op. hours Ea07 Display cylinder operating hours
Reset hour counter and set maintenance pre-alert threshold
Service heaterSteam process
heaterSteam titanium
b. Functions Autotest Eb01 Enable autotest Installer heaterSteam process
heaterSteam titanium
Enable preheat Eb02 Enable preheating
Set the water temperature to maintain Set the Off set
Installer heaterSteam process
heaterSteam titanium
Partial fi ll Eb03 Enable partial fi ll
Set partial fi ll time
Installer heaterSteam process
heaterSteam titanium
Drain due to inactivity Eb04 Enable drain due to inactivity
Set the inactivity threshold
Installer heaterSteam process
heaterSteam titanium
Periodical drain Eb05 Enable periodical drain cycles
Set the threshold for the periodical drain cycles
Installer heaterSteam process
heaterSteam titanium
Thermal shock Eb06 Enable thermal shock
Set the thermal shock threshold
Installer heaterSteam process
heaterSteam titanium
Digital output M5.2 Eb07 Enable the output relay for unit status (production) or mainte-
nance pre-alert
Installer heaterSteam process
heaterSteam titanium
Blower units Eb08 Set on and off delay for blower units Installer heaterSteam process
heaterSteam titanium
Export logs Eb09 Save the log of main variables to USB pen drive Service
Installer
heaterSteam process
heaterSteam titanium
Export alarms Eb10 Save alarm log to USB pen drive Service
Installer
heaterSteam process
heaterSteam titanium
c. Confi guration Main probe Ec01 Set the main probe: 0 to 1 V, 0 to 10 V, 2 to 10 V, 0 to 20 mA, 4 to
20 mA, NTC
Installer heaterSteam process
heaterSteam titanium
Limit probe Ec02 Set the limit probe: 0 to 1 V, 0 to 10 V, 2 to 10 V, 0 to 20 mA, 4 to
20 mA, NTC
Installer heaterSteam process
heaterSteam titanium
Wireless probes Ec03 Set the wireless probes (main/limit) Installer heaterSteam titanium
Wireless probe 1 Ec04 Set the weight of probe 1
Set the communication times
Installer heaterSteam titanium
Wireless probe 2 Ec05 Set the weight of probe 2
Set the communication times
Installer heaterSteam titanium
Wireless probe 3 Ec06 Set the weight of probe 3
Set the communication times
Installer heaterSteam titanium
Wireless probe 4 Ec07 Set the weight of probe 4
Set the communication times
Installer heaterSteam titanium
Number of evaporation
cycles before drain
Ec11 Set the number of evaporation cycles between two drain cycles Installer heaterSteam process
heaterSteam titanium
Variation in fi ll and drain
time
Ec12 Set the fi ll and drain time in relation to manufacturer default Installer heaterSteam process
heaterSteam titanium
Water hardness Ec13 Hardness value Installer heaterSteam process
heaterSteam titanium
No feedwater time Ec14 Set time to check for no water Installer heaterSteam process
heaterSteam titanium
High conductivity Ec15 Enable the high conductivity alarm
Set the alarm delay
Installer heaterSteam process
heaterSteam titanium
High conductivity Ec16 Set conductivity thresholds: warning, alarm and hysteresis Installer heaterSteam process
heaterSteam titanium
Remote ON input logic Ec22 Remote ON/OFF operating logic Installer heaterSteam process
heaterSteam titanium