CONTROL WITH TWO ACTIVE TEMPERATURE PROBES
short-circuit terminals M2.7 – M2.8 (jumper) to enable production;
alternatively connect terminals M2.7 – M2.8 to a remote contact (e.g.:
switch, timer,...);
connect the main active room probe to terminals M2.1, M2.2 (GND)
and M2.3 (+12Vdc);
connect the second active probe to terminals M2.5, M2.3 (+12Vdc) and
M2.6 (GND);
to enable control, set:
Screen ind. Screen desc. Parameter
Ea01 Control type Temperature (two probes)
Ea02 Control with 2 probes Set the weight of the two probes (0-100%)
Ea05 Modulating control Set: temperature set point (0-100 °C) (32-
212°F)
diff erential (2-20°C) (3.6-36°F)
Minimum production (0-100%)
Maximum production (0-100%)
Ec01 Main probe type Select from: 0-1V, 0-10V, 2-10V, 0-20mA,
4-20mA
Ec02 Second probe type Select from: 0-1V, 0-10V, 2-10V, 0-20mA,
4-20mA
The controller will calculate the weighted average between the two
probes. The weight of the two probes can also be set.
M2M9 M8
1 12345678212
OUT H / T
M
+ (G)
Main probe
OUT H / T
M
+ (G)
Second probe
Fig. 4.aa
The following probes can be connected:
CAREL probes for rooms DPWC111000
for air ducts DPDC110000; DPDC210000
for technical applications DPPC210000, DPPC210000
Note:: non-CAREL active probes can be connected to the controller.
_________________________________________________________
CONTROL WITH ONE NTC TEMPERATURE PROBE (passive)
short-circuit terminals M2.7 – M2.8 (jumper) to enable production;
alternatively connect terminals M2.7 – M2.8 to a remote contact (e.g.:
switch, timer,...);
connect the main NTC room probe to terminals M2.1, M2.2;
to enable control, set:
Screen index Screen description parameter
Ea01 Control type one temperature probe
Ea05 Modulating control Set:
temperature set point (0-100 °C)
(32-212°F)
diff erential (2-20°C) (3.6-36°F)
Minimum production (0-100%)
Maximum production (0-100%)
Ec01 Main probe type Set probe type: NTC
M2M9 M8
1 12345678212
Fig. 4.ab
CONTROL WITH TWO NTC TEMPERATURE PROBES (passive)
short-circuit terminals M2.7 – M2.8 (jumper) to enable production;
alternatively connect terminals M2.7 – M2.8 to a remote contact (e.g.:
switch, timer,...);
connect the main NTC room probe to terminals M2.1, M2.2;
connect the second NTC probe to terminals M2.5, M2.6;
to enable control, set:
Screen index Screen description parameter
Ea01 Control type Modulation with two temperature
probes
Ea02 Control with 2 probes Set the weight of the two probes
(0-100%)
Ea05 Modulating control Set:
temperature set point (0-100 °C)
(32-212°F)
diff erential (2-20°C) (3.6-36°F)
Minimum production (0-100%)
Maximum production (0-100%)
Ec01 Main probe type Set probe type: NTC
Ec02 Second probe type Set probe type: NTC
The controller will calculate the weighted average between the two
probes. The weight of the two probes can also be set.
M2M9 M8
1 12345678212
Fig. 4.ac
4.8 Alarm contact
The humidifi er controller is fi tted with a relay contact for remote signalling
of one or more faults or alarms. The alarm contact (250 Vac; max capacity: 2
A resistive - 2 A inductive) is connected to terminals M6.1, M6.2 and M6.3.
M1 M5 M6M12
132 31212 12
NC
NO
CO
L
N
Fig. 4.ad
M6.1 CO - Alarm common
M6.2 NC - NC alarm contact
M6.3 NO - NO alarm contact