humiSonic ventilation +0300063EN - rel. 1.3 - 14.05.2021
Mask Display description Notes Def. UOM Min Max Value description Type R/W
Fa04 Regulation
Ambient probe (AI7)
Type 0...1 V - 0...1 V 0...1 V¦ 0...5 V ¦
0…10 V ¦ NTC
I R/W
Offset 0.0 -100.0 100.0 I R/W
Min 0.0 0.0 100.0 I R/W
Max 100.0 0.0 100.0 I R/W
Alarm delay 0 s 0 999 I R/W
Fa05 Regulation Fa03=HYHU...
Ambient probe (TH)
Type rH%+T
Offset 0.0 -20.0 50.0 I R/W
Fa06 Regulation Fa01: reg.=...+lim.rH%
Limit probe (AI6)
Type 0...5 V - 0...1 V 0...1 V¦ 0...5 V I R/W
Offset 0.0 -100.0 100.0 I R/W
Min 0.0 0.0 100.0 I R/W
Max 100.0 0.0 100.0 I R/W
Alarm delay 10 s 0 999 I R/W
Fa07 Regulation Fa01: reg.=probe (+lim.rH%)
Ambient probe differential 10 rH%/°C 0 99.9 I R/W
Limit probe differential 10 rH% 0 99.9 I R/W
Fa08 Regulation Fa01: reg.=probe ...
Reg. hysteresis 10.0 % 0 99.9 I R/W
Fa09 Regulation Fa01: reg.=probe (+lim.rH%)
Max amb. H/T 80.0 rH%/°C 0 100.0 I R/W
Min amb. H/T 0.0 rH%/°C 0 100.0 I R/W
Max Lim. Hum. 100.0 rH% 0 100.0 I R/W
Min Lim. Hum. 0.0 rH% 0 100.0 I R/W
Fa10 Regulation Fa01: reg.=On/Off
Logic humidos. N.C. - N.C. N.O. N.C: production if closed contact I R/W
Fa11 Regulation
Mist modulation mode Serie - Serie Parallel See DIP-SWITCH settings I R
Mist modulation period 1 s 1 10 I R/W
Fa12 Enable preheating probe No - No Yes D R/W
Alarm delay 0 s 0 999 I R/W
Fa13 Preheat set point 28 °C -100 100 I R/W
Preheat differential 10 °C -100 100 I R/W
Fa14 PR% out type (output request) 0-5V - 0-5V 0-10V I R/W
b. Washings
Fb01 Washings
Time triggered Time or event
triggered (OR
condition)
Absolute time - Disabled Scheduled Disabled ¦ Absolute time ¦ Working/
No working ¦ Scheduled
I R/W
Event triggered Disabled - Disabled From request Disabled ¦ From digital input ¦ From
request
I R/W
Fb02 Washings
From mask Yes - Yes No Yes ¦ No I R/W
From BMS Yes - Yes No Yes ¦ No I R/W
Fb03 Work wash Fb01=working/ no
working
Enabled Yes No Yes Yes ¦ No I R/W
Work wash period 1 min 1 480 I R/W
Fb04 Nowork wash Fb01= working/no
working
Enabled Yes - No Yes Yes¦ No I R/W
Nowork period 24 h/m 1 480 I R/W
Next wash 24 h/m 1 480 I R/W
Fb05 Absolute Fb01= absolute
time
Period 24 h/m 0 999 I R/W
Next wash 24 h/m 0 999 I R/W
Fb06 Scheduled Fb01=Progr.
Start 00:00 hh/min 00:00 23:59 I R/W
Select day ? No No Yes D R/W
Every Monday Monday Sunday I R/W
Fb07 From DI Fb01=da DI
Input Humidostat Humidostat Rem. On/O D R/W
When Activ. event On --> O On --> O Off --> On D R/W
Fb08 From request Fb01=from
request
When request Rise - Rise Falls D R/W
Fb09 Wash settings Fb01=abs. time
Washing time 1 min 0 10 I R/W
Only if ready ? No No Yes D R/W
c. Settings
Fc01 Settings
Start delay 10 s 0 120
I R/W
Restart wait 10 min 1 60 I R/W
Fc02 Settings
Alarm relay logic N.O. - N.O. N.C. D R/W
Status relay Production Production Maintenance Production ¦ Maintenance I R/W
Logic N.O. - N.O. N.C. D R/W
Fc03 Settings
Drain valve in stand-by(*) Open - Open Closed D R/W
Drain delay in stand-by (*)=Open 0 min 0 60 I R/W
G. Service
a. Change language
Language Italian - English Italian D R/W