40
ENG
ir33plus +0300028EN rel. 1.1 - 05.05.2017
User Par. Description Models Def Min Max UOM Type CAREL SVP ModBus® R/W
rtc
C td1…8 Defrost 1 to 8 (press Set) SYFCH - - - - - - R/W
d__ Defrost 1 to 8 - day 0 0 11 day I 106/109/…/127 206/209/…/227 R/W
h__ Defrost 1 to 8 - hour 0 0 23 hour I 107/110/…128 207/210/…/228 R/W
n__ Defrost 1 to 8 - minute 0 0 59 min I 108/111/…129 208/211/…/229 R/W
C ton Light/aux on time SYFCH - - - - - - R/W
d__ Day 0 1 7 day I 130 230 R/W
h__ Hour 0 0 23 hour I 131 231 R/W
n__ Minute 0 0 59 minute I 132 232 R/W
C toF Light/aux o time SYFCH - - - - - - - R/W
d__ Day 0 1 7 day I 133 233 R/W
h__ Hour 0 0 23 hour I 134 234 R/W
n__ Minute 0 0 59 minute I 135 235 R/W
C tc Date/time (press Set) MSYFCH - - - - R/W
y__ Date/time: year 12 0 99 year I 1 101 R/W
m__ Date/time: month 8 1 12 month I 2 102 R/W
d__ Date/time: day of the month 1 1 31 day I 3 103 R/W
u__ Day of the week 1 1 7 day I 4 104 R/W
h__ Date/time: hour 0 0 23 hour I 5 105 R/W
n__ Date/time: minute 0 0 59 minute I 6 106 R/W
7.14 Variables only accessible via serial
connection
Description Type CAREL SVP Modbus R/W
Virtual probe A 3 3 R
Probe 1 reading A 4 4 R
Probe 2 reading A 5 5 R
Probe 3 reading A 6 6 R
Probe 4 reading A 7 7 R
Number of parameter sets available I 137 237 R
Digital input 1 status D 6 6 R
Digital input 2 status D 7 7 R
Virtual probe fault alarm D 9 9 R
Probe alarm 1 D 10 10 R
Probe alarm 2 D 11 11 R
Probe alarm 3 D 12 12 R
Probe alarm 4 D 13 13 R
Compressor status relay D 1 1 R
Defrost relay status D 2 2 R
Fan relay status D 3 3 R
AUX 1 relay status D 4 4 R
AUX 2 relay status D 5 5 R
Digital input 1 status D 6 6 R
Digital input 2 status D 7 7 R
Defrost status D 31 31 R
Defrost call command D 34 34 RW
Continuous cycle status D 35 35 R
Continuous cycle call command D 36 36 RW
Door status D 37 37 R
AUX activation command D 57 57 RW
Light activation command D 58 58 RW
Controller ON/OFF D 59 59 RW
Password I 14 114 RW
Virtual probe fault alarm D 9 9 R
Probe 1/2/3/4/5 fault alarm D 10/11/12/13/14 10/11/12/13/14 R
Low temperature alarm D 15 15 R
High temperature alarm D 16 16 R
Immediate external alarm D 17 17 R
Delayed external alarm D 18 18 R
Evaporator 1 defrost timeout alarm D 19 19 R
Evaporator 2 defrost timeout alarm D 20 20 R
Pump down timeout alarm D 21 21 R
Low pressure alarm D 21 21 R
High condenser temperature alarm D 24 24 R
Door open for too long alarm D 25 25 R
RTC error D 26 26 R
Control parameter EEPROM error D 27 27 R
Operating parameter EEPROM error D 28 28 R
HA HACCP alarm D 29 29 R
HF HACCP alarm D 30 30 R
Alarm autostart in pump down D 32 32 R