6 Tabella allarmi
Legenda tabella allarmi
*: se la sonda è impostata per la compensazione, in caso di avaria,
l’unità continua a funzionare.
ON*: nel caso la scheda espansione non sia presente.
EVD 1= EVD400 collegata al µC
2
(1° circ.)
EVD 2= EVD400 collegata all’espansione (2° circ.)
6 Table of alarms
Key to the table of alarms
*: if the probe is set for the compensation function, in the event of
probe faults, the unit continues to operate.
ON*: if the expansion card is not present.
• EVD 1= EVD400 connected to µC
2
(1st circ.)
• EVD 2= EVD400 connected to the expansion (2nd circ.)
64
µC
2
- cod. +030220420 - rel. 2.0 - 18.10.04
Tabella allarmi/
Table of alarms
Visual. Tipo di allarme Ripristino Compres Pompa Ventilat. Resist. Valv. Allarm Avviso Variabile Descrizione Variab. Tipo variab.
Allarm Alarm type Resetting Compres. Pump Fan Heater Valve Alarm Warning
Superv. Supervis
Var. Type
Alarm Superv. Superv. Variab.
display Variable description
HP1 Alta pressione Dipende da P05. OFF C1-2 - ON(60”) - - ON - 31 (R) Allarme circuito 1 Digital
High pressure Depends on P05 Circuit 1 alarm
HP2 Alta pressione Dipende da P05 OFF C3-4 - ON(60”) - - ON - 32 (R) Allarme circuito 2 Digital
High pressure Depends on P05 Circuit 1 alarm
LP1 Bassa pressione Dipende da P05 OFF C1-2 - OFF 1 - - ON - 31 (R) Allarme circuito 1 Digital
Low pressure Depends on P05 Circuit 1 alarm
LP2 Bassa pressione Dipende da P05 OFF C3-4 - OFF 2 - - ON - 32 (R) Allarme circuito 2 Digital
Low pressure Depends on P05 Circuit 2 alarm
TP Termico generale Dipende da P08 OFF OFF OFF - - ON - 35 (R) Allarme generale Digital
General overload Depends on P08 General warning
tC1 Termico circuito 1 Dipende da P08 OFF C1-2 - OFF 1 - - ON - 31 (R) Allarme circuito 1 Digital
Circuit 1overload Depends on P08 Circuit 1 alarm
tC2 Termico circuito 2 Dipende da P08 OFF C3-4 - OFF 2 - - ON - 32 (R) Allarme circuito 2 Digital
Circuit 2 overload Depends on P08 Circuit 2 alarm
LA Avviso Dipende da P08 - - - - - ON* ON 40 (R) Avviso generale Digital
Advice Depends on P08 General advice
FL Allarme flussostato Dipende da P08 OFF OFF OFF - - ON - 35 (R) Allarme generale Digital
Flow controller alarm Depends on P08 General warning
FLb Avviso pompa backup Automatico - - - - - - ON 40 (R) Avviso generale Digital
Backup pump warning Automatic General advice
E1 Allarme sonda. B1 Automatico OFF OFF OFF OFF - ON - 36 (R) Allarme sonde Digital
Probe B1 alarm Automatic Probe alarm
E2 Allarme sonda B2 Automatico OFF OFF OFF OFF - ON - 36 (R) Allarme sonde Digital
Probe B2 alarm Automatic Probe alarm
E3* Allarme sonda B3 Automatico OFF OFF OFF OFF - ON - 36 (R) Allarme sonde Digital
Probe B3 alarm Automatic Probe alarm
E4* Allarme sonda B4 Automatico OFF OFF OFF OFF - ON - 36 (R) Allarme sonde Digital
Probe B4 alarm Automatic Probe alarm
E5 Allarme sonda B5 Automatico OFF OFF OFF OFF - ON - 36 (R) Allarme sonde Digital
Probe B5 alarm Automatic Probe alarm
E6 Allarme sonda B6 Automatico OFF OFF OFF OFF - ON - 36 (R) Allarme sonde Digital
Probe B6 alarm Automatic Probe alarm
E7* Allarme sonda B7 Automatico OFF OFF OFF OFF - ON - 36 (R) Allarme sonde Digital
Probe B7 alarm Automatic Probe alarm
E8* Allarme sonda B8 Automatico OFF OFF OFF OFF - ON - 36 (R) Allarme sonde Digital
Probe B8 alarm Automatic Probe alarm
Hc1-4 Avviso ore C1-4 Automatico - - - - - - ON 37 (R) Avviso compress. Digital
Hour warning C1-4 Automatic Compressor advice
EPr Errore EEPROM Automatico - - - - - - ON 40 (R) Avviso generale Digital
in funzione
Automatic General advice
EEPROM error
during operation
EPb Errore EEPROM all’avvio Automatico OFF OFF OFF OFF OFF OFF OFF 35 (R) Allarme generale Digital
EEPROM error at the Automatic General warning
start-up
ESP Errore espansione Automatico OFF OFF OFF OFF OFF ON - 35 (R) Allarme generale Digital
Expansion Error Automatic General warning
EL1-2 Zero cross Automatico - - 100% - - ON* ON 42 (R) Avviso ventilatori Digital
Zero cross Automatic Fans advice
dF1-2 Errore sbrinamento Automatico - - - - - - ON 40 (R) Avviso generale Digital
Defrosting error. Automatic General advice
d1-2 Esecuzione defrost - - - - - - - - - Segnalazione a -
circuito interessato display
Defrost on circuit Signal on display
in question
A1 Allarme Ghiaccio Dipende da P05 OFF C1-2 - OFF 1 - - ON - 31 (R) Allarme circuito 1 Digital
circ. 1
Depends on P05 Alarm circuit 1
Frost alarm circ.1/2
A2 Allarme Ghiaccio circ. 2 Dipende da P05 OFF C3-4 - OFF 2 - - ON - 32 (R) Allarme circuito 2 Digital
Ice alarm circ.2 Depends on P05 Alarm circuit 2
Ht Alta temperatura Automatico - - - - - ON* ON 41 (R) Avviso temperatura Digital
High temperature Automatic
Temperature warning
continua/
continues...