Auxiliary (par. DOc)
The actuator can be activated/deactivated using a command from the supervisor and based on the
changeover in day/night status (linked to the curtain switch or the setting of the time bands);
activation/deactivation of the actuator is signalled by the AUX icon switching on/off. The AUX output to
be activated or deactivated based on the night/day time band can be selected (see parameters tS1...8,
tE1...8 and H9).
Code Description Def Min Max UOM User
User
terminal
DOc Assign auxiliary digital output - see DOA 0 0 4 - S NO
H9
Output switched with time bands
0 = Light
1 = AUX
0 0 1 - S NO
Auxiliary serving the MASTER on the SLAVES (par. DOd)
From the Master, the action of the auxiliary output is broadcast via LAN to the Slaves whose digital output
is configured with DOd greater than 0. Activation (or deactivation) of the actuator is signalled by the AUX
icon switching on (off) on the Slave user terminal.
Code Description Def Min Max UOM User
User
terminal
DOd
Assign auxiliary serving the Master on the Slaves digital output -
see DOA
0 0 4 - S NO
Light (par. DOE)
The actuator can be activated/deactivated directly using the functions on the user terminal, using a
command from the supervisor and based on the changeover in day/night status (linked to the
curtain/door switch or the setting of the time bands); activation/deactivation of the actuator is signalled
by the light icon switching on/off. The light output to be activated or deactivated based on the night/day
time band can be selected (see parameters tS1...8, tE1...8 and H9).
Code Description Def Min Max UOM User
User
terminal
DOE Assign light digital output - see DOA 4 0 4 - S NO
Light serving the Master on the Slaves (par. DOF)
From the Master, the action of the light output is broadcast via LAN to the Slaves whose digital output is
configured with DOF greater than 0. Activation (or deactivation) of the actuator is signalled by the light
icon switching on (off) on the Slave user terminal.
Code Description Def Min Max UOM User
User
terminal
DOF
Assign light serving the Master on the Slaves digital output -
see DOA
0 0 4 - S NO
Defrost (par. DOG)
The actuator is activated/deactivated based on the defrost settings (see the paragraph "Defrost").
Activation/deactivation of the actuator is signalled by the defrost icon switching on/off on the user
terminal.
Auxiliary evaporator defrost (par. DOH)
A heater can be activated for defrosting the main and auxiliary evaporator.
48|5. Functions
MPXone +0300086EN rel. 1.0– 04.09.2018