Code Description Def Min Max UOM User
User
terminal
PM2 MOP: integral time 10 0 240 s M NO
PM3
MOP: alarm delay
0 = function disabled
0 0 999 s S NO
PM4 MOP: function activation delay when starting control 2 0 240 s M NO
PM5
MOP: close solenoid valve
0/1 = No/Yes
0 0 1 - S NO
PM6 MOP: max suction temp. threshold 50 -50 50 °C/°F M NO
PL1 LOP: min saturated evap. temp. threshold -50 -50 50 °C/°F M NO
PL2 LOP: integral time 0 0 240 s M NO
PL3
LOP: alarm delay
0 = function disabled
0 0 240 s S NO
cP1 Initial valve position when control starts 30 0 100 % M NO
Pdd Initial valve position maintenance time after defrost 10 0 30 min S NO
dSb
Valve position during defrost
0: as defined by the type of defrost
1: forced closed
2 to 100: opening percentage
0 0 100 % M NO
PMP
Enable manual expansion valve positioning
0/1 = disabled/enabled
0 0 1 - S NO
PMu Manual valve position - 0 600 steps S NO
PSM Smooth Lines - enable function 0 0 1 - S NO
PLt Smooth Lines - offset to stop control below set point 2 0 10 °C/°F S NO
PHS Smooth Lines - max superheat offset 15 0 50 K S NO
PSd Derivative time (Smooth Lines) 0 0 100 s S NO
PSI Integral time (Smooth Lines) 120 0 800 s S NO
PSP Proportional gain (Smooth Lines) 5 0 100 - S NO
Solenoid/compressor
c0 Delay to enable solenoid/comp. and evap. fans on power-up 0 0 240 min M NO
c1 Min time between consecutive compressor starts 0 0 15 min M NO
c2 Min compressor OFF time 0 0 15 min M NO
c3 Min compressor ON time 0 0 15 min M NO
c4
ON time for duty setting operation (Toff = 15 minutes fixed)
0 = compressor/valve always OFF
100 = compressor/valve always ON
0 0 100 min M NO
cc
Running time in continuous cycle
0 = Disabled
1 0 15 hours M NO
c6 Low temp. alarm bypass time after continuous cycle 60 0 240 min M NO
Alarms
A0 High and low temp. alarm reset differential 2 0.1 20 °C/°F S YES
A1
Alarm thresholds (AL, AH) relative to the set point St or absolute
0/1 = relative /absolute
0 0 1 - S NO
A2
Alarm thresholds (AL2, AH2) relative to the set point St2 or absolute
0/1 = relative /absolute
0 0 1 - S NO
A10
Configure solenoid/comp. control during ext. alarm with fixed 15 min OFF time
0 = always OFF
100 = always ON
0 0 14 - S NO
A11
Delay time for delayed external alarm
0 = Signal-only alarm
0 0 14 - S NO
AA
Assign probe for high (AH) and low (AL) temperature alarms
0: Not configured
1: Air off (Sm)
2: Defrost (Sd)
3: Air on (Sr)
4: Superheated gas (tGS)
5: Reserved
1 0 13 - S YES