Code Description Def Min Max UOM User
User
terminal
/5
Unit of measure
0/1 = °C/barg/°F/psig
0 0 1 - S NO
/6
Display decimal point
0/1 = Yes/No
0 0 1 - S NO
/t
Display signals/alarms on remote display
0/1 = Disabled/Enabled
0 0 1 - S NO
/t1
Display on user terminal
0 = Terminal disabled
1 to 6 = Probe 1 to 6
7, 8 = Reserved
9 = Control probe
10 = Virtual probe
11 to 14 = Serial Probe 1 to 4
15 = Temperature set point
12 0 18 - S NO
/t2 Display on remote display - see /t1 12 0 14 - S NO
H5
Enable keypad and NFC functions
0/1 = Disabled/Enabled
1 0 1 - U NO
H8
Buzzer
0/1 = No/Yes
1 0 1 - U NO
Day/Night
tS1..8-d Start time band 1 to 8 day: day - see (td1...8-d) 0 0 11 day S NO
tS1..8- h Start time band 1 to 8 day: hours 0 0 23 hours S NO
tS1..8-n Start time band 1 to 8 day: minutes 0 0 59 minutes S NO
tE1..8-d End time band 1 to 8 day: day - see (td1...8-d) 0 0 11 day S NO
tE1..8- h End time band 1 to 8 day: hours 0 0 23 hours S NO
tE1..8-n End time band 1 to 8 day: minutes 0 0 59 minutes S NO