If the field value is in brackets (-17.0), it means that at the moment of printing the instrument was off-line, and the value refers to
the last reading effected. If the value field is replaced by asterisks, it means that the variable has never been acquired by the
peripheral.
(4) - Daily variables log report:
15/09/2000 13:53 Installation name Page: 1/4
10/09/2000 1: LT cabinet temperature probe
0’ 10’ 20’ 30’ 40’ 50’
---|--------------------------------------------------------------------------
0| ----- ----- ----- ----- ----- *****
1| -21.3 -21.1 -21.0 -20.7 -20.2 -20.0
2| -20.0 -19.9 -19.9 -19.5 -19.7 -19.9
3| -20.0 -20.1 -20.5 -20.7 -20.8 -21.0
4| -21.3 -21.1 -21.0 -20.7 -20.2 -20.0
5| -20.0 -19.9 -19.9 -19.5 -19.7 -19.9
6| -20.0 -20.1 -20.5 -20.7 -20.8 -21.0
7| -21.3 -21.1 -21.0 -20.7 -20.2 -20.0
8| -20.0 -19.9 -19.9 -19.5 -19.7 -19.9
9| -20.0 -19.9 -19.9 -19.5 -19.7 -19.9
10| -20.0 -19.9 -19.9 -19.5 -19.7 -19.9
11| -20.0 -19.9 -19.9 -19.5 -19.7 -19.9
12| -20.0 -20.1 -20.5 -20.7 -20.8 -21.0
13| -21.3 -21.1 -21.0 -20.7 -20.2 -20.0
14| -20.0 -20.1 -20.5 -20.7 -20.8 -21.0
15| -21.3 -21.1 -21.0 -20.7 -20.2 -20.0
16| -20.0 -20.1 -20.5 -20.7 -20.8 -21.0
17| -21.3 -21.1 -21.0 -20.7 -20.2 -20.0
18| -20.0 -19.9 -19.9 -19.5 -19.7 -19.9
19| -20.0 -19.9 -19.9 -19.5 -19.7 -19.9
20| -20.0 -20.1 -20.5 -20.7 -20.8 -21.0
21| -21.3 -21.1 -21.0 -20.7 -20.2 -20.0
22| -20.0 -20.1 -20.5 -20.7 -20.8 -21.0
23| -21.3 -21.1 -21.0 -20.7 -20.2 -20.0
The daily report shows the values of a determined variable for the entire day, at the specified sampling interval. The values
allowed are 10, 15 and 30 minutes.
Each page contains the report for 2 variables.
The dashes “-----“ mean that no value was saved at that moment, that is, PlantWatch was off or alternatively the value is no
longer present in the log.
If, on the other hand, the string “*****” is printed, it means that the variable was saved but the value was not acquired by the
peripheral, or alternatively the peripheral was off-line.
The string “?????” indicates the attempt to print variables that are not entered in the log, while !!!!!” indicates a serious error in
the recording of the data.