EasyManua.ls Logo

Carrier 19XR - Frame 9, 10 and Larger (19 Xr Product)

Carrier 19XR
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15
FRAME 9, 10 AND LARGER (19XR PRODUCT)
The 19XR units with Frame 9, 10, and larger contain:
PE-A - MOV on the AC precharge control circuit board
PE-A1 - MOV on the TVSS module
PE-A2 - Common mode capacitors on the AC common
mode filter circuit board
PE-B1 - Common mode capacitors on the line side and
motor side power interface circuit boards.
For solidly grounded equipment PE-A, PE-A1, PE-A2 are all con-
nected (in) and PE-B1 is disconnected (out). This is the default
setting for the drive. For high resistance ground system all jumpers
are disconnected (out). High resistance ground systems applica-
tions are non-standard and should be reviewed with Service Engi-
neering/Technical Service Manager and may affect warranty. See
Fig. 18-21.
Fig. 18 — 19XR, Frame 9, 10, and Larger, PE-A MOV
on AC Precharge Control Circuit Board
Fig. 19 — 19XR, Frame 9, 10, and Larger,
PE-A1 MOV on TVSS
Fig. 20 — 19XR, Frame 9, 10, and Larger, PE-A2,
Capacitors on AC Common Mode Filter Circuit Board
Fig. 21 — 19XR, Frame 9, 10, and Larger, PE-B1,
Common Mode Capacitors on Line Side and
Motor Side Power Interface Circuit Boards