Resettable
Fault
237 FdbkMsg Fiber 6
Feedback Msg Timeout Fiber 6.
Transmission of the feedback message
from M6 PLI transitioned from online to
offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and M6 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
0
Resettable
Fault
238 FdbkMsg Fiber 7
Feedback Msg Timeout Fiber 7.
Transmission of the feedback message
from M7 PLI transitioned from online to
offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and M7 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
0
Resettable
Fault
239 FdbkMsg Fiber 8
Feedback Msg Timeout Fiber 8.
Transmission of the feedback message
from M8 PLI transitioned from online to
offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and M8 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
0
Resettable
Fault
240 FdbkMsg Fiber 9
Feedback Msg Timeout Fiber 9.
Transmission of the feedback message
from M9 PLI transitioned from online to
offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and M9 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
0
Resettable
Fault
241 FdbkMsg Fiber 10
Feedback Msg Timeout Fiber 10.
Transmission of the feedback message
from L0 PLI transitioned from online to
offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and L0 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
0
Resettable
Fault
242 FdbkMsg Fiber 11
Feedback Msg Timeout Fiber 11.
Transmission of the feedback message
from L1 PLI transitioned from online to
offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and L1 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
0
Resettable
Fault
243 FdbkMsg Fiber 12
Feedback Msg Timeout Fiber 12.
Transmission of the feedback message
from L2 PLI transitioned from online to
offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and L2 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the control
pod fiber diagram on the Tables &
Graphics tab.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.