9 Minor Fault 9015 TP Sec Mtr Ctrl
Torque Prove Secondary Motor Control
Conflict. Torque proving has been
enabled but the user has not read and
understood the application concerns
related to configuration of the secondary
motor control port.
Read the ‘Attention’ statement in the
programming manual publication 750-
PM101 relating to the use of TorqProve
while the secondary motor control port
is configured.
Coast. Additional Fault Action. Fault
opens main circuit breaker: No. Fault
can automatically reset: No.
Emergency override response: 0:455
[Emerg Prot OVRD] bit 9 ‘TorqPrv
Flts’.
10/11
Resettable
Fault
10007
11007
TorqPrv Spd Band
Torque Prove Speed Band. The
difference between parameter 10:1914
[VRef Commanded] and parameter
10:1044 [Motor Vel Fb] has exceeded the
level in parameter 9:54 [Speed Dev Band]
for a time period greater than the time
programmed in parameter 9:55 [SpdBand
Intgrtr].
Increase parameter 10:906 [System
BW] or parameter 9:54 [Speed Dev
Band] and parameter 9:55 [SpdBand
Intgrtr].
Coast
10/11
Resettable
Fault
10010
11010
OverSpeed Limit
OverSpeed Limit. Motor speed has
exceeded the limit set by parameter
10:1904 [Overspeed Limit]. For forward
motor rotation, this limit is parameter
10:1898 [Vel Limit Pos] + parameter
10:1904 [Overspeed Limit]. For reverse
motor rotation, this limit is parameter
10:1899 [Vel Limit Neg] - parameter
10:1904 [Overspeed Limit]. Parameter
10:1042 [Vel Fb Active] determines the
motor operating speed.
Increase parameter 10:1904
[Overspeed Limit]. If operating in torque
mode, ensure no sudden loss of load.
For closed loop, verify encoder
configuration and installation.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: Yes. Emergency
override response: 0:455 [Emerg Prot
OVRD] bit 2 ‘MS Ctrl Flts’.
10/11
Non-Resettable
Fault
10015
11015
OverFreq Limit
Over Frequency Limit. Output frequency
is greater than or equal to 590 Hz or less
than or equal to –590 Hz.
Operate the drive within –590 Hz to 590
Hz range.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
10/11
Resettable
Fault
10016
11016
Phase U to Grnd
Phase U to Ground. A phase to ground
fault has been detected between the drive
and motor in this phase.
Rotate U/T1, V/T2, W/T3 connections.
If the problem follows the wire, suspect
a field wiring problem. If no change,
suspect a problem with the drive.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: 0:455 [Emerg Prot
OVRD] bit 2 ‘MS Ctrl Flts’.
10/11
Resettable
Fault
10017
11017
Phase V to Grnd
Phase V to Ground. A phase to ground
fault has been detected between the drive
and motor in this phase.
Rotate U/T1, V/T2, W/T3 connections.
If the problem follows the wire, suspect
a field wiring problem. If no change,
suspect a problem with the drive.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: 0:455 [Emerg Prot
OVRD] bit 2 ‘MS Ctrl Flts’.
10/11
Resettable
Fault
10018
11018
Phase W to Grnd
Phase W to Ground. A phase to ground
fault has been detected between the drive
and motor in this phase.
Rotate U/T1, V/T2, W/T3 connections.
If the problem follows the wire, suspect
a field wiring problem. If no change,
suspect a problem with the drive.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: 0:455 [Emerg Prot
OVRD] bit 2 ‘MS Ctrl Flts’.
10/11
Resettable
Fault
10019
11019
Phase UV Short
Phase UV Short. Excessive current has
been detected between these two output
terminals.
Rotate U/T1, V/T2, W/T3 connections.
If the problem follows the wire, suspect
a field wiring problem. If no change,
suspect a problem with the drive.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: 0:455 [Emerg Prot
OVRD] bit 2 ‘MS Ctrl Flts’.
10/11
Resettable
Fault
10020
11020
Phase VW Short
Phase VW Short. Excessive current has
been detected between these two output
terminals.
Rotate U/T1, V/T2, W/T3 connections.
If the problem follows the wire, suspect
a field wiring problem. If no change,
suspect a problem with the drive.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: 0:455 [Emerg Prot
OVRD] bit 2 ‘MS Ctrl Flts’.
10/11
Resettable
Fault
10021
11021
Phase WU Short
Phase WU Short. Excessive current has
been detected between these two output
terminals.
Rotate U/T1, V/T2, W/T3 connections.
If the problem follows the wire, suspect
a field wiring problem. If no change,
suspect a problem with the drive.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: 0:455 [Emerg Prot
OVRD] bit 2 ‘MS Ctrl Flts’.
10/11
Resettable
Fault
10022
11022
Phase
UNegToGrnd
Phase U Negative To Ground. A phase to
ground fault has been detected between
the drive and motor in this phase.
Rotate U/T1, V/T2, W/T3 connections.
If the problem follows the wire, suspect
a field wiring problem. If no change,
suspect a problem with the drive.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: 0:455 [Emerg Prot
OVRD] bit 2 ‘MS Ctrl Flts’.
10/11
Resettable
Fault
10023
11023
Phase VNegToGrnd
Phase V Negative To Ground. A phase to
ground fault has been detected between
the drive and motor in this phase.
Rotate U/T1, V/T2, W/T3 connections.
If the problem follows the wire, suspect
a field wiring problem. If no change,
suspect a problem with the drive.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: 0:455 [Emerg Prot
OVRD] bit 2 ‘MS Ctrl Flts’.
Table 7 — Fault Codes by Port (cont)
PORT
CONDITION
DISPLAY
TEXT
FAULT ACTION FAULT ACTION
TYPE CODE