46
10/11
Resettable
Fault
10118
11118
Ld00 Fail
D-Axis Inductance at 0 Pct OutOfRange.
Parameter 10:910 [Autotune] is set to 3
‘Rotate MtrID’ and the value measured by
the Autotune procedure for parameter
10:627 [u PM Ld at 0] is not in the range
of acceptable values (negative).
Verify motor nameplate data and rerun
the rotate motor ID test. If fault
continues, obtain the motor datasheet
from motor vendor.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: Yes. Emergency
override response: Cannot override
this fault.
10/11
Resettable
Fault
10119
11119
Ld100 Fail
D-Axis Inductance at 100 Pct
OutOfRange. Parameter 10:910
[Autotune] is set to 3 ‘Rotate MtrID’ and
the value measured by the Autotune
procedure for parameter 10:629 [u PM Ld
at 100] is not in the range of acceptable
values (negative).
Verify motor nameplate data and rerun
the rotate motor ID test. If fault
continues, obtain the motor datasheet
from motor vendor.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: Yes. Emergency
override response: Cannot override
this fault.
10/11
Resettable
Fault
10120
11120
Lq Fail
Q-Axis Inductance Out of Range.
Parameter 10:910 [Autotune] is set to 3
‘Rotate MtrID’ and the value measured by
the Autotune procedure for parameter
10:637 [u PM Lq at 25], 10:639 [u PM Lq
at 50], 10:641 [u PM Lq at 75], 10:643 [u
PM Lq at 100], 10:645 [u PM Lq at 125],
10:647 [u PM Lq at 150], 10:649 [u PM Lq
at 175], or 10:651 [u PM Lq at 200] is not
in the range of acceptable values. This
could happen if current fails to rise up or
decreases too fast due to abnormal
conditions.
Verify motor nameplate data and rerun
the rotate motor ID test. If fault
continues, obtain the motor datasheet
from motor vendor.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: Yes. Emergency
override response: Cannot override
this fault.
12
Resettable
Fault
12001 Image Wtchdg Flt
Image Watchdog Fault. Communication
between the main control board and the
image buffer in one of the power
peripherals (power layer interface board,
torque accuracy module, or DC
precharge board) has stopped
transmitting for 10 milliseconds.
Power down and then check the fiber-
optic communication connections.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
12
Resettable
Fault
12002 ConstantsMsgIvld
Constants Message Invalid Fault. The
constants header information did not
match the content of the power peripheral
(power layer interface board, torque
accuracy module, or DC precharge
board).
Cycle power.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
12
Non-Resettable
Fault
12003 Constants Chksum
Constants Checksum Fault. The
constants download failed the checksum
test by one of the power peripherals
(power layer interface board, torque
accuracy module, or DC precharge
board).
Cycle power.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
12
Non-Resettable
Fault
12004 NVS Checksum Flt
Nonvolatile Data Checksum Fault.
Checksum test failed for non-volatile data
for the DC precharge board.
Cycle power. If the fault persists,
replace the DC precharge board. See
the hardware service manual,
publication 750-TG100 for PowerFlex
755T or publication 750-TG101 for
PowerFlex 755TS products, for the
replacement procedure.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: 0:455 [Emerg Prot
OVRD] bit 7 ‘Board Faults’.
12
Resettable
Fault
12005 Power Supply UV
Power Supply Undervoltage. An
undervoltage event occurred in the local
(internal to the PIB) power supply. A
possible cause is the DC bus voltage,
which feeds the power supply, has
dropped below 400-v DC. This power
supply provides power to the power layer
interface board or DC precharge board (if
present).
Verify DC bus is present on the Mn
power module via the hardware
testpoints. If so, replace the Mn power
interface board (PIB). See hardware
service manual, publication 750-TG100
for PowerFlex 755T or publication 750-
TG101 for PowerFlex 755TS products,
for the replacement procedure.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: 0:455 [Emerg Prot
OVRD] bit 3 ‘MS Pwr Flts’.
12
Resettable
Fault
12006 Precharge Fault
Precharge Fault. Main control board
firmware did not indicate that bus voltage
was good within the specified time period
following closure of the precharge
contactor.
Check the timing of the rise of the DC
bus following precharge.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: 0:455 [Emerg Prot
OVRD] bit 3 ‘MS Pwr Flts’.
12
Resettable
Fault
12007 MCS CL BayOTmp
MCS Failed to Close or Wiring Bay
Overtemp. Two conditions can cause
this fault:
Condition 1: The molded case switch
(MCS) in the DC precharge has failed
to close when commanded.
Condition 2: The temperature in the
input bay or entry wiring bay has risen
too high. This condition can only
cause the fault before the drive or bus
supply has completed precharge.
Condition 1: Inspect the DC
precharge module and the thermal
sensor harness for the exit wiring
bay. Ensure MCS lockout device is
not closed. See the Service
Manual, publication 750-TG100 for
PowerFlex 755T or publication
750-TG101 for PowerFlex 755TS
products, for details.
Condition 2: Check the enclosure
filters and fans. Problems with the
baffling between these bay and
adjacent bays can be sources of
heat.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: 0:455 [Emerg Prot
OVRD] bit 3 ‘MS Pwr Flts’.
Table 7 — Fault Codes by Port (cont)
PORT
CONDITION
DISPLAY
TEXT
FAULT ACTION FAULT ACTION
TYPE CODE