45
10/11
Resettable
Fault
10101
11101
CntrlTask Wtchdg
Control Task Watchdog. The Control task
has failed to complete in the allotted
amount of time.
Clear faults. If the fault persists, rerun
firmware update and/or replace the
main control board. See the hardware
service manual, publication 750-TG100
for PowerFlex 755T or publication 750-
TG101 for PowerFlex 755TS products,
for the replacement procedure.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
10/11
Resettable
Fault
10102
11102
SystmTask Wtchdg
System Task Watchdog. The System
task has failed to complete in the allotted
amount of time.
Clear faults. If the fault persists, rerun
firmware update and/or replace the
main control board. See the hardware
service manual, publication 750-TG100
for PowerFlex 755T or publication 750-
TG101 for PowerFlex 755TS products,
for the replacement procedure.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
10/11
Resettable
Fault
10103
11103
1ms Task Wtchdg
1ms Task Watchdog. The 1-millisecond
task has failed to complete in the allotted
amount of time.
Clear faults. If the fault persists, rerun
firmware update and/or replace the
main control board. See the hardware
service manual, publication 750-TG100
for PowerFlex 755T or publication 750-
TG101 for PowerFlex 755TS products,
for the replacement procedure.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
10/11
Resettable
Fault
10104
11104
2ms Task Wtchdg
2ms Task Watchdog. The 2-millisecond
task has failed to complete in the allotted
amount of time.
Clear faults. If the fault persists, rerun
firmware update and/or replace the
main control board. See the hardware
service manual, publication 750-TG100
for PowerFlex 755T or publication 750-
TG101 for PowerFlex 755TS products,
for the replacement procedure.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
10/11
Resettable
Fault
10105
11105
10ms Task Wtchdg
10ms Task Watchdog. The 10-
millisecond task has failed to complete in
the allotted amount of time.
Clear faults. If the fault persists, rerun
firmware update and/or replace the
main control board. See the hardware
service manual, publication 750-TG100
for PowerFlex 755T or publication 750-
TG101 for PowerFlex 755TS products,
for the replacement procedure.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
10/11
Resettable
Fault
10107
11107
OverVoltage
Over Voltage. DC bus voltage exceeded
120% of the peak value of the rated
voltage for the product. (Peak value is the
AC rated voltage multiplied by 2).
Monitor DC bus voltage in parameter 0:3
[DC Bus Volts]. Possible causes include:
configuration of line side converter,
configuration of DC bus regulator, high
inertia loads, and fast decel times.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
10/11
Resettable
Fault
10109
11109
HeatSinkUnderTmp
Heatsink Under Temperature. Heatsink
temperature sensor is reporting a value
below –18.7°C. (–1.66°F) or the sensor
feedback circuit is open. See parameter
10:362 [Heatsnk Temp Pct] and/or
parameter 10:363 [Heatsnk Temp].
Verify that the ambient temperature is
within specification. See the technical
data, publication 750-TD100 for
PowerFlex 755T or publication 750-
TD104 for PowerFlex 755TS products.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: Yes. Emergency
override response: 0:455 [Emerg Prot
OVRD] bit 3 ‘MS Pwr Flts’.
10/11
Resettable
Fault
10110
11110
Autotune Inertia
Autotune Inertia Out of Range. The motor
or total inertia that is determined by the
Autotune inertia test function is out of
range. This condition only occurs during
an inertia test.
Verify motor nameplate data. Rerun
inertia Autotune.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
10/11
Non-Resettable
Fault
10111
11111
Inv App No Strt
Inverter Application Not Start. The motor
side inverter application failed to start in
the DSP.
Cycle power. If the fault persists, rerun
firmware update and/or replace the
main control board. See the hardware
service manual, publication 750-TG100
for PowerFlex 755T or publication 750-
TG101 for PowerFlex 755TS products,
for the replacement procedure.
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
10/11
Resettable
Fault
10112
11112
InvalidLoadRatio
Invalid Load Ratio. The total system
inertia result of the Autotune is less than
the value in parameter 10:900 [Motor
Inertia], which results in a negative load
ratio.
Determine if the value of parameter
10:900 [Motor Inertia] is too high. If
possible, uncouple the motor from the
load and perform the motor inertia
autotune test.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
10/11
Resettable
Fault
10114
11114
Jnt OverTemp Flt
Junction OverTemp Fault. The transistor
Junction Temperature of the power
module has exceeded the Fault
Temperature (varies by rating). Possible
causes include loads that require too
much current and power, improper
derating for temperature and altitude, and
obstructed airflow.
Verify motor nameplate data and drive
tuning for proper starting torque. Verify
that the drive is sized and derated
correctly. See the technical data,
publication 750-TD100 for PowerFlex
755T or publication 750-TD104 for
PowerFlex 755TS products.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: Yes. Emergency
override response: 0:455 [Emerg Prot
OVRD] bit 3 ‘MS Pwr Flts’.
Table 7 — Fault Codes by Port (cont)