Resettable
Fault
231 FdbkMsg Fiber 0
Feedback Msg Timeout Fiber 0.
Transmission of the feedback message
from M0 PLI transitioned from online to
offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and M0 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
0
Resettable
Fault
232 FdbkMsg Fiber 1
Feedback Msg Timeout Fiber 1.
Transmission of the feedback message
from M1 PLI transitioned from online to
offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and M1 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
0
Resettable
Fault
233 FdbkMsg Fiber 2
Feedback Msg Timeout Fiber 2.
Transmission of the feedback message
from M2 PLI transitioned from online to
offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and M2 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
0
Resettable
Fault
234 FdbkMsg Fiber 3
Feedback Msg Timeout Fiber 3.
Transmission of the feedback message
from M3 PLI transitioned from online to
offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and M3 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
0
Resettable
Fault
235 FdbkMsg Fiber 4
Feedback Msg Timeout Fiber 4.
Transmission of the feedback message
from M4 PLI transitioned from online to
offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and M4 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
0
Resettable
Fault
236 FdbkMsg Fiber 5
Feedback Msg Timeout Fiber 5.
Transmission of the feedback message
from M5 PLI transitioned from online to
offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and M5 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
Table 7 — Fault Codes by Port (cont)
PORT
CONDITION
DISPLAY
TEXT
FAULT ACTION FAULT ACTION
TYPE CODE