27
0
Resettable
Fault
27 Module Defaulted
Module Defaulted. A command to reset
parameter defaults on a single port has
been executed. This fault also sets when
secure erase has been completed for the
product. See code 18 ‘System Defaulted’
for reset of all ports.
Normal operation when parameters are
defaulted.
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
0
Resettable
Fault
29 Port 1 Adapter
Port 1 Adapter. The DPI communications
adapter in Port 1 has a fault. Port 1 is the
HIM cradle on the control pod.
See the event queue in Port 1.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: No. Fault can automatically
reset: No. Emergency override
response: 0:455 [Emerg Prot OVRD]
bit 10 ‘Pt1.3 Flts’.
0
Resettable
Fault
30 Port 2 Adapter
Port 2 Adapter. The DPI communications
adapter in Port 2 has a fault. Port 2 is
usually a HIM or a 1203-USB adapter.
See the event queue in Port 2.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: No. Fault can automatically
reset: No. Emergency override
response: 0:455 [Emerg Prot OVRD]
bit 10 ‘Pt1.3 Flts’.
0
Resettable
Fault
31 Port 3 Adapter
Port 3 Adapter. The DPI communications
adapter in Port 3 has a fault. Port 3 is
usually a HIM or a 1203-USB adapter.
See the event queue in Port 3.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: No. Fault can automatically
reset: No. Emergency override
response: 0:455 [Emerg Prot OVRD]
bit 10 ‘Pt1.3 Flts’.
0
Resettable
Fault
32 Port 4 Adapter
Port 4 Adapter. The DPI communications
adapter in Port 4 has a fault. Port 4 is
backplane option slot 4.
See the event queue in Port 4.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: No. Fault can automatically
reset: No. Emergency override
response: 0:455 [Emerg Prot OVRD]
bit 11 ‘Port 4 Flts’.
0
Resettable
Fault
33 Port 5 Adapter
Port 5 Adapter. The DPI communications
adapter in Port 5 has a fault. Port 5 is
backplane option slot 5.
See the event queue in Port 5.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: No. Fault can automatically
reset: No. Emergency override
response: 0:455 [Emerg Prot OVRD]
bit 12 ‘Port 5 Flts’.
0
Resettable
Fault
34 Port 6 Adapter
Port 6 Adapter. The DPI communications
adapter in Port 6 has a fault. Port 6 is
backplane option slot 6.
See the event queue in Port 6.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: No. Fault can automatically
reset: No. Emergency override
response: 0:455 [Emerg Prot OVRD]
bit 13 ‘Port 6 Flts’.
0
Resettable
Fault
38 Port 4 DPI Loss
Port 4 DPI Loss. The DPI
communications adapter in Port 4 has
stopped communicating with main control
board. Port 4 is a backplane connection,
slot 4.
Verify that the backplane ports are free
of debris and mounting screws are
secured. Reseat option card. If problem
persists, contact technical support.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: No. Fault can automatically
reset: No. Emergency override
response: 0:455 [Emerg Prot OVRD]
bit 11 ‘Port 4 Flts’.
0
Resettable
Fault
39 Port 5 DPI Loss
Port 5 DPI Loss. The DPI
communications adapter in Port 4 has
stopped communicating with main control
board. Port 5 is a backplane connection,
slot 5.
Verify that the backplane ports are free
of debris and mounting screws are
secured. Reseat option card. If problem
persists, contact technical support
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: No. Fault can automatically
reset: No. Emergency override
response: 0:455 [Emerg Prot OVRD]
bit 12 ‘Port 5 Flts’.
0
Resettable
Fault
40 Port 6 DPI Loss
Port 6 DPI Loss. The DPI
communications adapter in Port 4 has
stopped communicating with main control
board. Port 6 is a backplane connection,
slot 6.
Verify that the backplane ports are free
of debris and that mounting screws are
secure. Reseat the option module. If
the problem persists, contact technical
support.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: No. Fault can automatically
reset: No. Emergency override
response: 0:455 [Emerg Prot OVRD]
bit 13 ‘Port 6 Flts’.
Table 7 — Fault Codes by Port (cont)
PORT
CONDITION
DISPLAY
TEXT
FAULT ACTION FAULT ACTION
TYPE CODE