The Carrier VFD option Start-Up and Service Manual is intended 
for trained and qualified service personnel and is to be used during 
start-up, operation, and maintenance of Rockwell/Allen-Bradley 
PF755L drive.
ABBREVIATIONS AND EXPLANATIONS
Frequently used abbreviations in this manual include: 
Required Publications
The Carrier VFD option Start-Up and Service Manual must be 
used with the following manuals:
• Latest version of the PowerFlex Drives with TotalFORCE 
Control Manuals
• Latest revision of the Start-Up, Operation, and Maintenance 
Instructions for 19XRV or 23XRV with PIC6 Controls
Getting Assistance from Rockwell Automation
Contact the local Rockwell Automation sales office with any 
questions or problems relating to the products described in this 
manual. For technical support on drives, call the HVAC Hotline at 
1-440-646-3434 Select Option 3 (Technical Support), then select 
Option 5 (More Options), Direct Dial Code for PowerFlex 755 
drives is 500.
Before calling, have the following information available from the 
Allen-Bradley data nameplate located inside the enclosure on the 
right wall. See Fig. 1.
• Allen-Bradley ID or CAT. NO.
• Carrier VFD Code (Carrier Part Number)
• Allen-Bradley serial number
Fig. 1 — Allen Bradley Power Module Data Nameplate
IDENTIFYING DRIVE COMPONENTS
Chiller control schematics and VFD schematics are included in 
APPENDIX A — WIRING SCHEMATICS.
Opening the VFD Access Door
1. Using recommended screwdriver (6.4 mm [0.25 in.] flat or 
T20 star), open access door. See Fig. 2.
2. Check to be sure that voltage between DC+ and DC– and 
from each DC terminal to the chassis is zero before proceed-
ing. See Fig. 3.
Fig. 2 — Opening Access Door
Fig. 3 — Check DC Bus Terminals
DC — Direct Current
DPI — Drive Peripheral Interface
ENET — Ethernet
HMI — Human Machine Interface
ICVC — International Chiller Visual Controller
IGBT — Insulated Gate Bipolar Transistor
I/O — Inputs/Outputs
IP — Internet Protocol
ISM — Integrated Starter Module
MCB — Main Control Board
MOV — Metal Oxide Varistor
PE — Protective Earthing Conductor
PIC — Product Integrated Control
PWM — Pulse Width Modulation
SIO — Sensor Input/Output
STS — Status
VFD — Variable Frequency Drive
WARNING
DC bus capacitors retain hazardous voltages after input power 
has been disconnected. After disconnecting input power, wait 
five (5) minutes for the DC bus capacitors to discharge and 
then check the voltage with a voltmeter rated for the DC bus 
voltage to ensure the DC bus capacitors are discharged before 
touching any internal components. Failure to observe this 
precaution could result in severe bodily injury or loss of life.
An isolated multimeter will be needed to measure DC bus 
voltage and to make resistance checks. The drive’s DC bus 
capacitors retain hazardous voltages after input power has been 
disconnected.
WARNING
Before removing the drive enclosure, open access door and 
verify that the DC bus voltage has dropped to zero by checking 
the terminals behind the access door. Failure to observe this 
precaution could result in severe bodily injury or loss of life.
Wall Mount Drives
19MV
Floor Mount Drives (Typical)
19XR6
1
L1 L2 L3
O
I
2
DC+ DC–
0V
0V
Lockout/Tagout
Multimeter
DC Bus Test 
Terminals
Located Inside
Access Door