39
0
Resettable
Fault
244 FdbkMsg Fiber 13
Feedback Msg Timeout Fiber 13.
Transmission of the feedback message
from L3 PLI transitioned from online to
offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and L3 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
0
Resettable
Fault
245 FdbkMsg Fiber 14
Feedback Msg Timeout Fiber 14.
Transmission of the feedback message
from L4 PLI transitioned from online to
offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and L4 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
0
Resettable
Fault
246 FdbkMsg Fiber 15
Feedback Msg Timeout Fiber 15.
Transmission of the feedback message
from L5 PLI transitioned from online to
offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and L5 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
0
Resettable
Fault
247 FdbkMsg Fiber 16
Feedback Msg Timeout Fiber 16.
Transmission of the feedback message
from L6 PLI transitioned from online to
offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and L6 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
0
Resettable
Fault
248 FdbkMsg Fiber 17
Feedback Msg Timeout Fiber 17.
Transmission of the feedback message
from L7 PLI transitioned from online to
offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and L7 PLI for damage. Replace the
fiber cable and/or fiber transceiver if
needed. See the hardware service
manual, publication 750-TG100 for
PowerFlex 755T or publication 750-
TG101 for PowerFlex 755TS products,
for the replacement procedure. See the
control pod fiber diagram on the Tables
& Graphics tab.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
0
Resettable
Fault
249 FdbkMsg Fiber 18
Feedback Msg Timeout Fiber 18.
Transmission of the feedback message
from L8 PLI transitioned from online to
offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and L8 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
Table 7 — Fault Codes by Port (cont)
PORT
CONDITION
DISPLAY
TEXT
FAULT ACTION FAULT ACTION
TYPE CODE