68
FREESTANDING DRIVES (19XR PRODUCT)
For 19XRV Freestanding drives a different tool is used. The same
procedure of removing hardware to isolate the LCL, converter, or
inverter module is used so the module can slide out and be safely
removed from the drive using the PowerFlex 750-Series Service
Cart. See Fig. 43.
Fig. 43 — Service Cart
Rockwell catalog 750-IN105 contains the service cart require-
ments based on PF755TL size and needs. It is recommended to
ensure that a site has access to a service cart as without it the LCL
filter modules and power modules cannot be replaced.
Adequate service clearance in front and to the side of a freestand-
ing PF755TL drive is required. See Fig. 44.
Fig. 44 — Clearance Requirement
Conversion kits for specific PF755TL frame size 8-10 are sold
separately. Consult with Rockwell for details.
Follow all safety procedures instructions provided with the Ser-
vice Cart to remove either the LCL Filter Module, converter mod-
ule, or inverter module.
The service cart (Fig. 45) can be docked in the cabinet (below fil-
ter modules) once use is completed.
Component Weights (without packaging):
Fig. 45 — Service Cart Use
20-750-MI4-xnnnxnnn 20-750-MI1-xnnnxnnn
Power
Module
250 lb (113 kg) 312 lb (142 kg)
600 Amp/480-v 740 Amp/480-v 1000–1300Amp/480-v
LCL Filter
Modules
385 lb (175 kg) 470 lb (213 kg) 710 lb (322 kg)
914 mm
(36 in.)
152 mm
(6 in.)
Top View
8