31
0
Non-Resettable
Fault
314 Inv DCP Fbr Cfg
Invalid DCP Fiber Configuration. Main
control board firmware has detected an
invalid DC precharge fiber connection.
Power down. Examine the fiber-optic
cable connections between the DC
precharge modules and the Mn power
modules power layer interface (PLI)
circuit boards for damage. Verify that
the DC precharge fiber-optic cable is
inserted into the PDI socket on the Mn
PLI circuit boards. See the installation
instructions, publication 750-IN100, for
information on fiber-optic cable
connections.
—
0
Non-Resettable
Fault
315 Inv ACP Fbr Cfg
Invalid ACP Fiber Configuration. Main
control board firmware has detected an
invalid AC precharge connection to the
fiber interface circuit board.
Power down. Examine the fiber-optic
cable connections between the AC
precharge module and the fiber
interface circuit board for damage.
Verify that the AC precharge fiber-optic
cable is inserted into the correct socket
on the fiber interface circuit board. See
the installation instructions, publication
750-IN100, for information on fiber-
optic cable connections.
—
0
Non-Resettable
Fault
316 Inv MVFB Fbr Cfg
Invalid TAM Fiber Configuration. Main
control board firmware has detected an
invalid torque accuracy module (TAM)
connection to the fiber interface circuit
board.
Power down and examine the fiber-
optic cable connections between the
TAM and the fiber interface circuit
board for damage. Verify that the TAM
fiber-optic cable is inserted into the
correct socket on the fiber interface
circuit board. See the installation
instructions, publication 750-IN100, for
information on fiber-optic connections.
—
0
Non-Resettable
Fault
318 Unknown Device
Unknown Device In System. Main control
board firmware has detected an unknown
backplane option card.
Examine the status indicators on the
option cards for errors. Power down
and check backplane connections.
Reseat option card if needed. Refer to
the associated manual of the option
card for troubleshooting.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: No. Fault can automatically
reset: No. Emergency override
response: Cannot override this fault.
0
Non-Resettable
Fault
319 DPI Card Wrg Slt
DPI Card In Wrong Slot. Main control
board firmware has detected a DPI
backplane option board in a non-DPI
backplane option slot. Only the lower slots
(4, 5, and 6) support DPI. Backplane
option cards that require DPI cannot
function in slots 7 and 8.
Power down and examine the
placement of backplane option cards in
the control pod. Review the slot
restrictions in the Installation
Instructions.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: No. Fault can automatically
reset: No. Emergency override
response: Cannot override this fault.
0
Non-Resettable
Fault
320 Vlt Class Mismth
Voltage Class Mismatch. Main control
board firmware has detected a voltage
class mismatch between power
peripherals (power modules, LCL filter
modules, or precharge modules). For
example, one power peripheral is of the
400/480-v voltage class while the others
are 600/690-v.
Power down and examine the voltage
class of the power peripherals: torque
accuracy module (TAM), AC precharge
module (ACP), DC precharge module
(DCP), and power modules.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: No. Fault can automatically
reset: No. Emergency override
response: Cannot override this fault.
0
Non-Resettable
Fault
321 Inv Dev in Cfg
Invalid Device In Configuration. Main
control board firmware has detected
power peripherals (power modules, LCL
filter modules, or precharge modules) that
is not a valid peripheral type.
Power down and examine the power
peripherals and the fiber-optic cable
connections on the fiber interface circuit
board.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: No. Fault can automatically
reset: No. Emergency override
response: Cannot override this fault.
0
Non-Resettable
Fault
322 Op Mode Mismth
Operational Mode Mismatch. Main control
board firmware has detected an
operational mode mismatch.
Power down and verify that the power
mode plugs on the power layer
interface (PLI) circuit board are
connected properly.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: No. Fault can automatically
reset: No. Emergency override
response: Cannot override this fault.
0
Non-Resettable
Fault
323 Inv FR Id
Invalid Frame Rating ID. Main control
board firmware has detected an invalid
frame rating ID.
Contact technical support. —
0
Non-Resettable
Fault
324 CatalogId NotFnd
Catalog ID Not Found. Main control board
firmware has failed to find the catalog ID.
Cycle power. Verify fiber-optic cable
connections. Update firmware.
—
0
Non-Resettable
Fault
325 Inv Conn Opt
Invalid Connected Option. Main control
board firmware has detected an invalid
LCL filter configuration. The LCL filter
module does not match the expected
channel assignment.
Power down and verify current sense
board (CSB) jumpers are set properly
for each channel.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: No. Fault can automatically
reset: No. Emergency override
response: Cannot override this fault.
0
Non-Resettable
Fault
326 Prllel Fr Mismth
Parallel Frame Mismatch. Main control
board firmware has detected an invalid
combination of line side converter power
modules and LCL filter modules.
Power down and verify that the LCL
filter subframes match the converter
subframes and the correct filter size is
connected to match the power layer
interface (PLI) board configuration.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: No. Fault can automatically
reset: No. Emergency override
response: Cannot override this fault.
Table 7 — Fault Codes by Port (cont)
PORT
CONDITION
DISPLAY
TEXT
FAULT ACTION FAULT ACTION
TYPE CODE