Carrier 30HL - Troubleshooting Common Issues; Compressor Start-Up & Operation Problems; Oil Loss & Suction Line Freezing; High Pressure & Continuous Operation

Carrier 30HL
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Compressor
does
not
run
j
!
i
'
Power
line
open
j
Reset
circuit
breaker.
Control
circuit
breaker
tripped
|
i
Check
control
circuit
for
ground
or
short.
Reset
breaker.
Safety
tripped
Reset.
Tripped
power
breaker
Check
the
controls.
Find
cause
of
trip
and
reset
breaker.
Condenser
circulating
pump
not
running
Power
off
restart.
Pump
binding
free
pump.
Incorrect
wiring
rewire.
Pump
motor
burned
out
replace.
Loose
terminal
connection
Check
connections.
Improperly
wired
controls
Check
wiring
and
rewire.
Low
line
voltage
Check
line
voltage
determine
location
of
voltage
drop
and
remedy
deficiency.
Compressor
motor
defective
Check
motor
winding
for
open
or
short.
Replace
compressor,
if
necessary.
Seized
compressor
Replace
compressor.
Compressor
cycles
on
low-
pressure
control
Low-pressure
control
erratic
in
action
Raise
differential
setting.
Check
capillary
for
pinches.
Replace
control.
Compressor
suction
valve
leaking
Replace
valve
plate.
Compressor
suction
shutoff
valve
partially
closed
Open
valve.
Low
refrigerant
charge
Add
refrigerant.
Plugged
compressor
suction
strainer
Clean
strainer
or
replace.
Compressor
loses
oil
Leak
in
system
Repair
leak.
Mechanical
damage
(blown
piston
or
broken
discharge
valve)
Repair
damage
or
replace
compressor.
Oil
trapped
in
line
Check
piping
for
oil
traps.
Crankcase
heaters
not
energized
during
shutdown
Check
wiring
and
crankcase
heater
relay.
Replace
heater
if
necessary.
Frosted
suction
line
Expansion
valve
admitting
excess
refrigerant
Compressor
cycles
on
high-
pressure
control
High-pressure
control
erratic
in
action
Check
capillary
tube
for
pinches.
Set
control
as
required.
Compressor
discharge
valve
i
partially
closed
Open
valve,
or
replace
if
defective.
i
Air
in
system
Purge.
S
Condenser
scaled
1
Clean
condenser.
J
Condenser
water
pump
or
fans
not
1
operating
Start
pump
repair
or
replace
if
defective.
Unit
operates
long
or
continuously
1
Low
refrigerant
charge
Add
refrigerant.
1
Control
contacts
fused
Replace
control.
1
Air
in
system
1
Purge.
1
Partially
plugged
or
plugged
I
Clean
or
replace.
expansion
valve
or
strainer
Defective
insulation
Replace
or
repair.
Service
load
too
high
Keep
doors
and
windows
closed.
inefficient
compressor
Check
valves,
replace
if
necessary.